| System Specifications |
|---|
| FACP: Mircom FX-2000 FACP Location: Main Entrance Vestibule System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR (FACP) 24VDC (boosters) System Coding: Temporal Strobes Synchronized: No Date of last known Upgrade: 2019 Most Recent Known Modification: N/A Year Opened: 2000 |
Parke at Fish Creek is an office building located at 14505 Bannister Road, Calgary, Alberta. The building was completed in 2000, and the fire alarm system was upgraded in 2019; the notification appliances remain original.
System Specifications (2019-present)
FACP
The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Mircom's Advanced addressable protocol, and the system coding is temporal.
Booster Panels
There are Edwards BPS booster power supplies in the main entrance vestibule and second floor corridor.
The unit 105 data room has an Edwards BPS6A 6-amp booster power supply.
The third floor data room has a Mircom INX-10A addressable 10-amp booster power supply.
All Edwards boosters are fed off NAC 4 of the main panel.
Notification Appliances
Most notification appliances are Edwards 439D-10AWC vibrating bells (10" gong) mounted on Edwards 403-5A-R strobe plates (15cd).
There are Edwards MB10-24 motor bells (10" gong) mounted on the aforementioned strobe plates on the renovated part of the 2nd floor, and are also found as deficiency replacements.
The third floor has Mircom BL-10B motor bells (10" gong) mounted on Wheelock RSSP-24MCW-FR strobe plates (red, set to 15cd) from a renovation.
Initiating Devices
Pull Stations
All pull stations are Mircom MS-401AP addressable single-action pull stations.
Automatic Detection Devices
There are Mircom MIX-2251APA addressable photoelectric smoke detectors at the top of each stairwell, return air plenums and at the top of the elevator shaft.
There are Mircom MIX-5251RAPA addressable 135°F fixed-temperature/rate-of-rise heat detectors in the janitor and electrical rooms on each floor, and the parkade telecom, electrical, elevator machine, storage and sprinkler rooms.
All detectors are mounted on System Sensor B210LPA bases.
The air handling units have System Sensor DNRA duct smoke detector housings with Mircom MIX-2251APA addressable photoelectric heads.
Modules
There are Mircom MIX-M500MAPA addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are Mircom MIX-M500RAPA addressable relay modules serving various purposes.
There are System Sensor M500XA isolator modules on the SLC.
EOLs
There are Mircom MP-300 end-of-line resistor plates on all sprinkler and signal circuits.