| System Specifications |
|---|
| FACP: Notifier NFS2-3030C FACP Location: Main Electrical Room System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: Mid-2010s Year Opened: 1975 |
The Pinebrook Golf & Country Club is a country club and golf course located at 166 Pinebrook Way SW, in Calgary, Alberta, Canada. This page will cover the main building, which is the only building with a fire alarm system. The building was built in 1975, and the fire alarm system was upgraded in the mid-2010s.
System Specifications (2010s-present)
FACP
The building is protected by a Notifier NFS2-3030C addressable fire alarm system. The panel is located in the main electrical room. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.
Annunciators
There is a Notifier LCD-160 annunciator at the basement stair entrance.
Notification Appliances
Most notification appliances are System Sensor "SpectrAlert Advance" P2RA horn/strobes (red, wall-mount, set to 15cd).
There are System Sensor PC2RKA weatherproof horn/strobes (red, ceiling-mount) outside under the breezeway.
Renovated areas have System Sensor "L-Series" P2RLA horn/strobes (red, wall-mount, bilingual lettering, set to 15cd).
Initiating Devices
Pull Stations
All indoor pull stations are Notifier NBG-12LX addressable dual-action pull stations.
The patio has one Notifier MPS-950B conventional single-action pull station, and one Notifier N-MPS-SC conventional single-action pull station; both are wired to a Notifier FMM-1A addressable monitor module.
Automatic Detection Devices
There are Notifier FSP-851A addressable photoelectric smoke detectors in all stairwells and elevator lobbies.
There are Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detectors in many areas.
There are Notifier FST-851HA addressable 190°F fixed-temperature heat detectors in all kitchens and most mechanical rooms.
There is a Notifier FST-851A addressable 135°F fixed-temperature heat detector in the basement mechanical room.
All aforementioned detectors except those in elevator lobbies are mounted on System Sensor B210LPA bases; elevator lobby devices are mounted on System Sensor B200SRA sounder bases.
There is a System Sensor DNRA duct smoke detector housing equipped with a Notifier FSP-851A addressable photoelectric head on the main air handling unit.
Modules
There are Notifier FMM-1A addressable monitor modules supervising the two kitchen suppression systems, and the sprinkler system's tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
EOLs
There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.