| System Specifications |
|---|
| FACP: EST iO500 FACP Location: Main Entrance Vestibule System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR (FACP) 24VDC (Boosters) System Coding: Temporal Strobes Synchronized: Yes, Genesis Date of last known Upgrade: N/A Year Opened: 2016 |
Pomeroy Inn & Suites Vermilion is a hotel located at 4111 51 Street, in Vermilion, Alberta, Canada. The hotel was built in 2016, and the fire alarm system is original.
System Specifications
FACP
The building is protected by an EST iO500 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs EST's Signature addressable protocol, and the system coding is temporal.
Booster Panels
There are Edwards BPS6A 6-amp booster power supplies in some electrical rooms.
Notification Appliances
Most common areas have Edwards "Genesis" G1F-HDVM horn/strobes (white, wall-mount, FIRE marking, set to 15cd).
The pool area has Edwards WG4RF-HVMC weatherproof horn/strobes (red, wall-mount, FIRE marking).
All guest rooms have Edwards G1F-VM remote strobes (white, wall-mount, FIRE marking, set to 15cd) and Edwards 683-1C silenceable mini-horns (white).
Initiating Devices
Pull Stations
All pull stations are EST SIGA-270 addressable single-action pull stations.
Automatic Detection Devices
There are EST SIGA-PS addressable photoelectric smoke detectors throughout all corridors.
There are EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors in some areas.
All aforementioned detectors are mounted on EST SIGA-SB bases.
There is an EST "SuperDuct" SIGA-SD addressable photoelectric duct smoke detector on the main air handling unit.
Modules
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.
There are EST SIGA-CC1 addressable control modules triggering all booster panels.
There are EST SIGA-IM addressable isolator modules on the SLC.
There are Edwards IDM signal isolator modules on all insuite circuits.
EOLs
There are Edwards EOL-P1 end of line resistor plates on all sprinkler and Class-B signal circuits.