System Specifications
FACP: Mircom FX-2000 w/QX-5000
FACP Location: Main Floor Loading Dock
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC/70VRMS
System Coding: 120BPM (1200Hz?)
Strobes Synchronized: No
Date of last known Upgrade: 2004
Year Opened: 1978

Princes Island Place is a mid-rise residential building in downtown Calgary located at 815 4 Ave SW.

The building was built in 1978, and the fire alarm system was upgraded in 2004.

System Specifications

FACP

The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located in the main floor loading dock. The system runs Mircom's CLIP addressable protocol, and is connected to a Mircom QX-5000 voice evacuation panel that feeds speakers in the hallway and suites. The QX-5000 does a march time tone for evac with no messages.

Notification Appliances

There are Mircom SP-104A-70 speakers (square, 4") mounted in hallways and in suites.

There are also Mircom FS-240R strobes (red, wall-mount, 15cd) mounted in the hallway.

Initiating Devices

Pull Stations

All pull stations are Mircom MS-401AD addressable single action pull stations.

Automatic Detection Devices

There is a Mircom MIX-5251RAPA addressable 135°F fixed-temperature/rate-of-rise heat detector mounted in the entryway of each suite.

There are Mircom MIX-2251APA addressable photoelectric smoke detectors in hallways and common areas.

All aforementioned detectors are mounted on System Sensor B210LPA bases.
There are System Sensor 5601A conventional 135°F fixed-temperature/rate-of-rise heat detectors throughout the parkade, individually wired to Mircom MIX-M501MA addressable monitor modules.

Modules

There are Mircom MIX-M500MA addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are Mircom MIX-M500RA addressable relay modules serving various purposes.
There are System Sensor ISO-XA isolator modules on the SLC.

EOLs

There are Mircom MP-300 and Simplex 2081-9018C end-of-line resistor plates on all sprinkler and signal circuits.