| System Specifications |
|---|
| FACP: Notifier AFP-200 FACP Location: P1 Main Electrical Room System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: No Date of last known Upgrade: N/A Most Recent Known Modification: N/A Year Opened: 2000 |
Residences of Mount Royal is an apartment building located at 881 15 Ave SW, in Calgary, Alberta, Canada. The building is owned and operated by the Equium Group. The building was built in 2000, and the fire alarm system is original.
System Specifications
FACP
The building is protected by a Notifier AFP-200 addressable fire alarm system. The panel is located in the P1 main electrical room. The system runs Notifier's CLIP addressable protocol, and the system coding is temporal.
Annunciators
There is a Notifier LCD2-80 annunciator in the apartment main entrance vestibule, and there is a Notifier LCD-80TM annunciator in the parkade entrance vestibule beside Dollarama.
Booster Panels
There are three Notifier FCPS-24 6-amp booster power supplies; two in the 3rd floor garbage room, and one on the Dollarama mezzanine.
Notification Appliances
Common Areas
Most notification appliances are System Sensor "SpectrAlert" P2415A horn/strobes (red, wall-mount, 15cd).
Some areas have System Sensor "SpectrAlert Advance" P2RA horn/strobes (red, wall-mount, set to 15cd) and System Sensor "L-Series" P2RLA horn/strobes (red, wall-mount, set to 15cd) as deficiency replacements.
Suites
All suites have a mix of System Sensor PA400SW-A, System Sensor "SpectrAlert Advance" MHWZA, and Mircom MH-S25WA silenceable mini-horns (white).
All suites also have a mix of System Sensor "SpectrAlert" S2415WA, System Sensor "SpectrAlert Advance" SWA, and System Sensor "L-Series" SWLA remote strobes (white, wall-mount, 15cd fixed or set).
Initiating Devices
Pull Stations
Most pull stations are Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules.
There is a Notifier NBG-12LX addressable dual-action pull station on the 3rd floor Plus 15 as a deficiency replacement.
There is a Notifier N-MPS-SA addressable single-action pull station by the boiler room as a deficiency replacement.
Automatic Detection Devices
There are Notifier CPX-551A and Notifier FSI-851A addressable ionization smoke detectors throughout all residential corridors, at the top of each stairwell, and in each elevator lobby.
Some areas have Notifier FSP-851A and Notifier FSP-951A-IV addressable photoelectric smoke detectors as deficiency replacements; FSP-851A detectors are also installed at the top of some elevator shafts.
There are Notifier FDX-551RA and Notifier FST-851RA addressable 135°F fixed-tempertature/rate-of-rise heat detectors at the top of some elevator shafts, and in all mechanical, garbage, electrical and storage rooms. All aforementioned detectors are mounted on a mix of System Sensor BX501, B710LPA, B210LPA and B300A-6-IV bases.
There are Notifier DHX-502A addressable ionization smoke detectors on all air handling and makeup air units.
Modules
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier FCM-1A addressable control modules triggering all booster panels.
EOLs
There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.