| System Specifications |
|---|
| FACP: Notifier NFS2-640C FACP Location: Parkade Electrical Room System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 70VRMS (audible) 24VDC (visual) System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: 2014 Year Opened: 2006 |
River Vista is an apartment building located at 9707 106 St NW, Edmonton, Alberta. The building opened in 2006, and the fire alarm system is original with a panel replacement in 2014.
System Specifications (2006-present)
FACP
The building is protected by a Notifier NFS2-640C addressable fire alarm system. The panel is located in the parkade electrical room. The system runs Notifier's FlashScan addressable protocol, and is equipped with Notifier's "Digital Voice Command" voice evacuation system. The system coding is temporal.
Annunciators
There is a Notifier LCD-80TM annunciator in the entrance vestibule, with multiple ACM-24AT annunciators, an FHS firefighter's telephone and an RM-1 microphone.
Booster Panels
There is a mix of the following booster panels on most floors.
- Notifier PSE-6C
- Notifier FCPS-24C
- Notifier FCPS-24S8C
Notification Appliances
Most notification appliances are System Sensor "SpectrAlert" SP2C2415WA speaker/strobes (white, ceiling-mount, 15cd).
There are System Sensor "SpectrAlert Advance" SPSCWA speaker/strobes (white, ceiling-mount, set to 15cd) on floors L and 6 as deficiency replacements.
There is a System Sensor P2RKA weatherproof horn/strobe (red, wall-mount, set to 75cd) at the top of the roof.
Initiating Devices
Pull Stations
All pull stations are Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules.
Automatic Detection Devices
There are Notifier FSI-851A addressable ionization smoke detectors throughout the building.
There is a Notifier FSP-951RA addressable photoelectric smoke detector on floor L as a deficiency replacement.
The 7th floor has a Notifier FSP-951A addressable photoelectric smoke detector as a deficiency replacement.
The garbage, sprinkler and electrical rooms have Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detectors.
All detectors are mounted on Notifier B710LPA bases.
The roof storage rooms have FDD CF-135 conventional 135°F fixed-temperature heat detectors, wired to Notifier FMM-101A addressable monitor modules.
Modules
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier FTM-1A fire phone modules supervising all fire phones.
There are Notifier ISO-XA isolator modules on the SLC.
Firefighter's Telephones
There are Notifier FT-300N firefighter's telephones on each floor.
EOLs
There are Notifier EOL-CR end-of-line resistor plates on all conventional, sprinkler and signal circuits.