Seton Professional Centre West

From FireAlarmPedia
System Specifications
FACP: Simplex 4100ES
FACP Location: Main Entrance
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 70.7VRMS (Audible)
24VDC (Visual)
System Coding: Temporal Tone + Message?
Strobes Synchronized: Yes, SmartSync
Date of last known Upgrade: N/A
Year Opened: 2016

Seton Professional Centre West is a professional building located at 3815 Front St SE, in Calgary, Alberta, Canada. The building was built in 2016, and the fire alarm system is original.

System Specifications[edit | edit source]

FACP[edit | edit source]

The building is protected by a Simplex 4100ES addressable fire alarm system. The panel is located at the main entrance. The system runs Simplex’s IDNet addressable protocol, and is equipped with voice evacuation. The evacuation signal is likely a temporal tone and a voice message.

Notification Appliances[edit | edit source]

Most notification appliances are Simplex “TrueAlert” 4906-9157 speaker/strobes (white, ceiling-mount, set to 70V/15cd).
Areas requiring additional audible signaling coverage have Simplex 4902-9721CA remote speakers (white, ceiling-mount, set to 70V).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Simplex 4099-9001 addressable single-action pull stations.

Automatic Detection Devices[edit | edit source]

There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors in some areas, mounted on Simplex 4098-9792 bases.

Modules[edit | edit source]

There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Simplex 4090-9002 addressable relay modules serving various purposes.
There are Simplex 4090-9116 addressable isolator modules on all SLCs.

EOLs[edit | edit source]

There are Simplex 2081-9040C end of line resistor plates on all sprinkler and signal circuits.