System Specifications
FACP: EST QuickStart QS4
FACP Location: Main Entrance
System Type: Two-Stage Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VFWR (FACP)
24VDC (Boosters)
System Coding: 20BPM (Alert)
Temporal (Alarm)
Strobes Synchronized: No
Date of last known Upgrade: N/A
Most Recent Known Modification: N/A
Year Opened: 1983, 1998

The Sheraton Cavalier is a hotel located at 2620 32 Ave NE, in Calgary, Alberta, Canada. The building was built in 1983, and was expanded in 1998. The fire alarm system is mostly original.

System Specifications

Please note that this information is accurate to 2022.

FACP

The building is protected by an EST QuickStart QS4 conventional fire alarm system. The panel is located at the main entrance. The system is configured for two-stage operation. The alert signal coding is 20BPM, and the alarm signal coding is temporal.

Booster Panels

There are three Edwards BPS6AC 6-amp booster power supplies by the main FACP.

Notification Appliances

Most notification appliances are Edwards "Adaptahorn" 881-D remote horns (red).
There are Edwards "Integrity" 757-5A-T horn/strobes (red, wall-mount, 15cd) in some areas.
Some areas have Edwards 202-5A-T remote strobes (red, wall-mount, 15cd).
Some areas have Edwards "Genesis" G1R-HD remote horns (red, no marking) as deficiency replacements.
Some areas have Edwards G1R-VM remote strobes (red, wall-mount, no marking, set to 15cd) as deficiency replacements.

Initiating Devices

Pull Stations

All pull stations are Edwards 270-GAO conventional two-stage single-action pull stations.

Automatic Detection Devices

There are System Sensor C2W-BA conventional photoelectric smoke detectors throughout most areas.
There are System Sensor 5601A conventional 135°F fixed-temperature/rate-of-rise heat detectors in some areas.

EOLs

There are Edwards EOL-P1 end of line resistor plates on all circuits.