| System Specifications |
|---|
| FACP: Mircom FA-106R FACP Location: Main Entrance Vestibule System Type: Single-Stage Conventional System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Temporal Strobes Synchronized: N/A Date of last known Upgrade: 1993 Most Recent Known Modification: 2021, FACP/Some Detectors Year Opened: 1972 |
Southview Community Association is a community centre located at 2020 33 St SE, in Calgary, Alberta, Canada. The building was built in 1972, and the fire alarm system was upgraded in 1993; the FACP and some detectors were replaced in 2021.
System Specifications (1993-present)
FACP
The building is protected by a Mircom FA-106R conventional fire alarm system. The panel is located in the main entrance vestibule. The system coding is temporal.
Notification Appliances
All notification appliances are Edwards 439D-6AWC vibrating bells (6" gong).
Initiating Devices
Pull Stations
All pull stations are Edwards 275-C111 conventional single-action pull stations.
Automatic Detection Devices
There are Mircom TD-135 conventional 135°F fixed-temperature heat detectors in all bar areas and most storage rooms.
There are Mircom TD-200 conventional 200°F fixed-temperature heat detectors in the main furnace room and in all kitchens.
There are Edwards 245A conventional 135°F fixed-temperature heat detectors in the garage and skate shack.
There are System Sensor 5604A conventional 194°F fixed-temperature heat detectors in all furnace rooms and some storage rooms.
There is a System Sensor 5601A conventional 135°F fixed-temperature/rate-of-rise heat detector in the main entrance vestibule.
The kitchen suppression system is wired to the fire alarm system.
EOLs
There are Edwards EOL-P1 end of line resistor plates on all initiating and signal circuits.
There is a Notifier EOL-CR end of line resistor plate on the kitchen suppression system circuit.