Starlight Casino

From FireAlarmPedia
System Specifications
FACP: Edwards EST3
FACP Location: Unknown
System Type: Two-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 70.7VRMS (Audible)
24VDC (Visual)
System Coding: Unknown
Strobes Synchronized: Yes, Genesis
Date of last known Upgrade: 2018
Year Opened: 1983, 1999

Starlight Casino is a casino located in West Edmonton Mall, at #2710 8882 170 St NW, in Edmonton, Alberta, Canada. The building was built in 1983, and was expanded in 1999. The fire alarm system was upgraded during a renovation in 2018.

System Specifications (2018-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by an Edwards EST3 addressable fire alarm system. The panel location is unknown. The system runs Edwards’ Signature addressable protocol, is configured for two-stage operation, and is equipped with voice evacuation. The messages and/or tones are unknown at this time.

Notification Appliances[edit | edit source]

Most notification appliances are Edwards “Genesis” GC-S7VM speaker/strobes (white, ceiling-mount, no marking, 70V, set to 15cd).
Some areas have Edwards G4-S7VM speaker/strobes (white, wall-mount, no marking, 70V, set to 15cd).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.

Automatic Detection Devices[edit | edit source]

There are EST SIGA-PS addressable photoelectric smoke detectors in some areas, mounted on EST SIGA-SB bases.

Modules[edit | edit source]

There are EST SIGA-CT2 addressable dual-input monitor modules supervising the sprinkler system’s tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.
There are EST SIGA-IM addressable isolator modules on all SLCs.

EOLs[edit | edit source]

There are Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.