| System Specifications |
|---|
| FACP: Mircom FX-2000 FACP Location: Fire Control Room System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 70.7VRMS (Audible) 24VFWR (Visual) System Coding: Temporal Tone Strobes Synchronized: No Date of last known Upgrade: N/A Most Recent Known Modification: 2026, Speaker Year Opened: 2015 |
The Arch is a high-rise apartment building located at 1115 9 St SW, in Calgary, Alberta, Canada. The building is owned and operated by Boardwalk. The building was built in 2015, and the fire alarm system is original.
System Specifications
FACP
The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located in the fire control room, behind the mail room on the main floor. The system runs Mircom's CLIP addressable protocol, and is equipped with Mircom's QX-5000 voice evacuation system. The evacuation signal is a temporal tone.
Booster Panels
There are Mircom BPS-1100 11-amp booster power supplies in the electrical rooms on the 4th, 8th, 12th, 16th, 20th and 23rd floors.
Notification Appliances
All common areas have System Sensor "SpectrAlert Advance" SPSCWA speaker/strobes (white, ceiling-mount, set to 70V/15cd).
All suite bedrooms have Mircom SP-404-70A remote speakers (white, 4" square) equipped with Mircom SSW-100 silence switches.
All stairwells have Mircom SP-204A-70W remote speakers (white, 4" square).
Initiating Devices
Pull Stations
All pull stations are Mircom MS-401AD addressable single-action pull stations.
Automatic Detection Devices
There are Mircom MIX-2251APA addressable photoelectric smoke detectors in all corridors, at the top and on every third floor of each stairwell, and in all elevator lobbies.
There are Mircom MIX-5251RAPA addressable 135°F fixed-temperature/rate-of-rise heat detectors at the top of each elevator shaft.
All detectors are mounted on System Sensor B210LPA bases.
There are System Sensor "InnovAir Flex" DNRA duct smoke detector housings equipped with Mircom MIX-2251APA addressable photoelectric heads on all makeup air units.
Firefighter's Telephones
There are Mircom FT-300A fire phones at each stairwell on each floor.
Modules
There are Mircom MIX-M500MAPA addressable monitor modules supervising the fire pump's run/trouble contacts, the generator's run/trouble contacts, all boosters, and the sprinkler system's tamper and flow switches.
There are Mircom MIX-M500RAPA addressable relay modules serving various purposes.
There are Mircom MIX-M500FPA fire phone modules controlling all fire phones.
There are System Sensor M500XA isolator modules on all 4 SLCs.
EOLs
There are Mircom MP-300 end of line resistor plates on all circuits supervised by monitor modules, and on all signal circuits.