System Specifications
FACP: Notifier NFS-320C
FACP Location: Main Entrance Vestibule
System Type: Two-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: 20BPM (Alert)
Temporal (Alarm)
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: 2013
Year Opened: 1978

Dartmouth Place is an office building located at 480 36 Ave SE, in Calgary, Alberta, Canada. The building is owned and operated by The City of Calgary, and houses offices for various city departments. The building was built in 1978, and the fire alarm system was upgraded in 2013.

System Specifications (2013-present)

FACP

The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier's FlashScan addressable protocol, and is configured for two-stage operation. The alert coding is 20BPM, and the alarm coding is temporal.

Booster Panels

There are three Notifier FCPS-24S6C 6-amp booster power supplies on the system; two are located in comm rooms, and one is located in the sprinkler room.

Notification Appliances

Most indoor notification appliances are System Sensor "SpectrAlert Advance" PC4WA horn/strobes (white, ceiling-mount, set to 15cd).
Some areas have System Sensor P4RA horn/strobes (red, wall-mount, set to 15cd).
For outdoor notification, there is a System Sensor SRKA weatherproof remote strobe (red, wall-mount) outside the main entrance.

Initiating Devices

Pull Stations

All pull stations are Notifier N-MPS-2A addressable two-stage single-action pull stations.

Automatic Detection Devices

There are Notifier FSP-851A addressable photoelectric smoke detectors at the top of each stairwell.
There are Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detectors in the main electrical room, and in all comm rooms.
All detectors are mounted on System Sensor B210LPA bases.

Modules

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.

EOLs

There are Notifier EOL-CR end of line resistor plates on all sprinkler circuits.
All signal circuits are wired as Class-A.