More actions
| System Specifications |
|---|
| FACP: Notifier NFS-320C FACP Location: Main Entrance System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: 2010s Most Recent Known Modification: N/A Year Opened: 1954 |
Trapped Escape Room Kensington is an escape room located at 1139 Kensington Road NW, in Calgary, Alberta, Canada. The building was built in 1954, and was converted into an escape room in the 2010s. The fire alarm system was upgraded as part of the 2010s conversion.
System Specifications (2010s-present)
FACP
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located at the main entrance. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.
Notification Appliances
Most notification appliances are System Sensor "SpectrAlert Advance" P2RA horn/strobes (red, wall-mount, set to 15cd).
Some areas have System Sensor SRA remote strobes (red, wall-mount, set to 15cd).
Initiating Devices
Pull Stations
All pull stations are Notifier NBG-12LX addressable dual-action pull stations.
Automatic Detection Devices
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout most areas.
There are Notifier FST-851A addressable 135°F fixed-temperature heat detectors in some areas.
All aforementioned detectors are mounted on System Sensor B210LPA bases.
There are System Sensor "Innovair Flex" DNRA duct smoke detector housings equipped with Notifier FSP-851A addressable photoelectric heads on all air handling units.
Modules
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on the SLC.
EOLs
There are Notifier EOL-CR end of line resistor plates on all signal circuits.