System Specifications
FACP: Simplex 4100ES
FACP Location: Unknown
System Type: Two-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 70.7VRMS (Audible)
24VDC (Visual)
System Coding: 20BPM Tone + Message(Alert)
Slow Whoop + Message (Alarm)
Strobes Synchronized: Yes, SmartSync
Date of last known Upgrade: 2020
Most Recent Known Modification: N/A
Year Opened: 1986

The University of Calgary is a public research university located at 2500 University Drive NW, in Calgary, Alberta, Canada. This page will cover the Scurfield Hall building, which was built in 1986. The fire alarm system was upgraded in 2020.

System Specifications (2020-present)

FACP

The building is protected by a Simplex 4100ES addressable fire alarm system. The panel location is unknown. The system runs Simplex's IDNet addressable protocol, is equipped with voice evacuation, and is configured for two-stage operation. The alert signal is a 20BPM tone, and the alarm signal is slow whoop. There are custom messages for both stages.
This panel is part of a campus-wide 4120 network.

Annunciators

There are Simplex 4603-9101 annunciators at each entrance.

Notification Appliances

All notification appliances are Simplex "TrueAlert" 4906-9157 speaker/strobes (white, ceiling-mount, set to 70V/15cd).

Initiating Devices

Pull Stations

All pull stations are Simplex 4099-9004CA addressable two-stage single-action pull stations.

Automatic Detection Devices

There are Simplex "TrueAlarm" 4098-9714 addressable photoelectric smoke detectors in some areas, mounted on Simplex 4098-9792 bases.

Modules

There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are Simplex 4090-9002 addressable relay modules serving various purposes.
There are Simplex 4090-9116 addressable isolator modules on all SLCs.

EOLs

There are Simplex 2081-9040C end of line resistor plates on all sprinkler and signal circuits.