| System Specifications |
|---|
| FACP: Notifier NFS2-3030C FACP Location: CACF Room System Type: Two-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 25VRMS (Audible) 24VDC (Visual) System Coding: 20BPM (Alert) Temporal Whoop (Alarm) Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: N/A Most Recent Known Modification: N/A Year Opened: 2011 |
Verve Aspen Woods is a senior living and retirement facility located at 10 Aspenshire Drive SW, in Calgary, Alberta, Canada. The building was built in 2011, and the fire alarm system is original.
System Specifications
FACP
The building is protected by a Notifier NFS2-3030C addressable fire alarm system. The panel is located in the CACF room on the main floor. The system runs Notifier's FlashScan addressable protocol, is equipped with Notifier's "Digital Voice Command" (DVC) voice evacuation system, and is configured for two-stage operation. The alert signal is a 20BPM tone, and the alarm signal is temporal whoop.
Annunciators
There are Notifier LCD-160 annunciators in each stairwell on the main floor, behind the reception desk, and at the 2nd floor nurse's station.
Notification Appliances
All notification appliances are System Sensor "SpectrAlert Advance" SPSRA speaker/strobes (red, wall-mount, set to 25V/15cd).
Initiating Devices
Pull Stations
All pull stations are Notifier N-MPS-2A addressable two-stage single-action pull stations.
Automatic Detection Devices
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout all corridors, at the top of each stairwell, in each electrical closet, and at the top of each elevator shaft.
There are Notifier FSP-851TA addressable photoelectric smoke/135°F fixed-temperature heat detectors in all suites on floors 2-4.
There are Notifier FPTI-951A addressable multi-criteria detectors in all suites on the main floor.
There are Notifier FST-851A addressable 135°F fixed-temperature heat detectors in some areas and in all elevator pits.
There are Notifier FST-851HA addressable 190°F fixed-temperature heat detectors in the kitchen and in some mechanical rooms.
There is a Notifier FST-951A addressable 135°F fixed-temperature heat detector in the kitchen as a deficiency replacement.
All aforementioned 851-series detectors are mounted on System Sensor B210LPA bases.
All aforementioned 951-series detectors are mounted on System Sensor B300A-6 bases.
There are System Sensor "Innovair Flex" DNRA duct smoke detector housings equipped with Notifier FSP-851A addressable photoelectric heads on all air handling units.
Modules
There are Notifier FDM-1A addressable dual-input monitor modules supervising the generator's run/trouble contacts, and the sprinkler system's low air, tamper and flow switches.
There are Notifier FMM-1A addressable monitor modules supervising the kitchen suppression systems.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on all SLCs.
There are Notifier RSM-1A silence modules on all suite signal circuits.
EOLs
There are Notifier EOL-CR end of line resistor plates on all circuits supervised by monitor modules, and on all signal circuits.