Viking Rentals Centre

From FireAlarmPedia
System Specifications
FACP: EST iO500
FACP Location: Main Electrical Room
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR (FACP)
24VDC (Booster)
System Coding: Temporal
Strobes Synchronized: Yes, Genesis
Date of last known Upgrade: 2015
Year Opened: 2006/2015

Viking Rentals Centre (formerly Pason Centennial Arenas or Okotoks Centennial Arenas) is a twin arena complex located at 204 Community Way, Okotoks, Alberta. The Green Arena, built in 2006, has a capacity of 1500, and is home to the Okotoks Oilers of the British Columbia Hockey League (BCHL). The Gold Arena, built in 2015, is home to numerous Okotoks minor hockey teams, and also houses a leisure ice rink. The fire alarm system is original to both portions, excluding the main FACP.

System Specifications (2006-present)

FACP

The building is protected by an EST iO500 addressable fire alarm system. The panel is located in the main electrical room. The system runs EST's Signature addressable protocol, and the system coding is temporal.
This panel replaced an EST QuickStart QS1.

Annunciators

There is an EST RLCD-C annunciator paired with an EST RLED24 annunciator in the main entrance vestibule. Both annunciators are mounted inside an EST RA-ENC2 enclosure.

Booster Panels

There is likely at least one Edwards BPS6A 6-amp booster power supply on the system.

Notification Appliances

All indoor notification appliances are Edwards "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no lettering, set to 15cd).
For outdoor notification, there is an Edwards CS405-7A-T weatherproof remote strobe (red, wall-mount, 15/75cd) outside the main entrance.

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270 addressable single-action pull stations.

Automatic Detection Devices

There are EST SIGA-PS addressable photoelectric smoke detectors in the following areas of the Green Arena: telephone rooms, at the top of all stairwells, and in some other areas.

There are Edwards SIGA-PD addressable photoelectric smoke detectors at the top of each Gold Arena stairwell, and in some other rooms.

There are EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors in some areas, such as electrical and mechanical rooms, and likely at the top of the elevator shaft.

All aforementioned detectors are mounted on SIGA-SB bases.

There are EST SIGA-DH duct smoke detector housings equipped with EST SIGA-PS addressable photoelectric heads on all air handling units.

Modules

There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.

There are EST SIGA-CR addressable relay modules serving various purposes.

There are likely EST SIGA-IM addressable isolator modules on at least one SLC.

EOLs

There are Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.