More actions
| System Specifications |
|---|
| FACP: Simplex 4100U FACP Location: Main Entrance Vestibule System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, SmartSync Date of last known Upgrade: N/A Most Recent Known Modification: N/A Year Opened: 2005 |
Walmart Supercentre is a chain of hypermarkets headquartered in Bentonville, Arkansas. This particular store is located at 5750 2 Ave, in Edson, Alberta, Canada. The building was built in 2005, and the fire alarm system is original.
System Specifications
FACP
The building is protected by a Simplex 4100U addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Simplex's IDNet addressable protocol, and the system coding is temporal.
Notification Appliances
Most notification appliances are Simplex "TrueAlert" 4906-9127 horn/strobes (red, wall-mount, set to 15cd).
Some areas, including washrooms, have Simplex 4906-9101 remote strobes (red, wall-mount, set to 15cd).
Throughout the storefront, horn/strobes and strobes are mounted on pillars in an alternating pattern on all 4 sides.
Initiating Devices
Pull Stations
All pull stations are Simplex 4099-9001 addressable single-action pull stations.
Automatic Detection Devices
There are Simplex "TrueAlarm" 4098-9714 addressable photoelectric smoke detectors in some areas, mounted on Simplex 4098-9792 bases.
Modules
There are Simplex 4090-9001 addressable monitor modules supervising all kitchen suppression systems, and the sprinkler system's tamper and flow switches.
There are Simplex 4090-9002 addressable relay modules serving various purposes.
There are Simplex 4090-9116 addressable isolator modules on the SLC.
EOLs
There are Simplex 2081-9040C end of line resistor plates on all kitchen suppression, sprinkler and signal circuits.