System Specifications |
---|
FACP: Simplex 4007ES FACP Location: Front Entrance System Type: Single-Stage Conventional System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Continuous Strobes Synchronized: No Date of last known Upgrade: 2010s Year Opened: 1999 |
Waterton International Hostel is a hostel on Cameron Falls Drive, Waterton, AB. It consists of the main building, which also houses a recreation centre, as well as nine guest houses, all built in 1999. The main building’s fire alarm system is mostly original, and all guest houses fire alarm systems are original.
System Specifications (Main Building) (1999-present)[edit | edit source]
FACP[edit | edit source]
The building is protected by a Simplex 4007ES conventional fire alarm system. The panel is located at the front entrance. The system coding is continuous.
This panel replaced a Notifier System 500 in the late 2010s.
Notification Appliances[edit | edit source]
All common area notification appliances are Wheelock MB-G6-24 motor bells (6” gong) mounted on Wheelock RSSP-2415W strobe plates (red, 15cd).
Each living unit has a System Sensor “SpectrAlert” S2415A remote strobe (red, wall-mount, 15cd).
For exterior notification, there is a Wheelock MB-G6-24 motor bell (6” gong) outside the entrance.
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
Most pull stations are Notifier NFM-950B conventional single-action pull stations.
There are some Edwards 270-SPO conventional single-action pull stations.
Automatic Detection Devices[edit | edit source]
There are System Sensor 1400A conventional ionization smoke detectors in most areas.
Some areas have System Sensor “i3” C2W-BA conventional photoelectric smoke detectors.
There are Simplex “TrueAlarm” 4098-9601 conventional photoelectric smoke detectors mounted to Simplex 4098-9788 bases as deficiency replacements.
All kitchens have Edwards 281C conventional 135°F fixed-temperature/rate-of-rise heat detectors.
EOLs[edit | edit source]
There are Notifier EOL-CR end-of-line resistor plates on all circuits.
System Specifications (Wildflower House) (1999-present)[edit | edit source]
System Specifications |
---|
FACP: Notifier SFP-400B FACP Location: Main Entrance Vestibule System Type: Single-Stage Conventional System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Continuous Strobes Synchronized: No Date of last known Upgrade: N/A Year Opened: 1999 |
FACP[edit | edit source]
The building is protected by a Notifier SFP-400B conventional fire alarm system. The panel is located in the main entrance. The system coding is continuous.
Notification Appliances[edit | edit source]
All notification appliances are Wheelock MB-G6-24 motor bells (6” gong) mounted on Wheelock RSSP-2415W strobe plates (red, 15cd).
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are Notifier NFM-950B conventional single-action pull stations.
Automatic Detection Devices[edit | edit source]
There are System Sensor “i3” C2W-BA conventional photoelectric smoke detectors throughout.
EOLs[edit | edit source]
There are Notifier EOL-CR end-of-line resistor plates on all circuits.
System Specifications (Mountain House) (1999-present)[edit | edit source]
System Specifications |
---|
FACP: Notifier SFP-400B FACP Location: Main Entrance Vestibule System Type: Single-Stage Conventional System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Continuous Strobes Synchronized: No Date of last known Upgrade: N/A Year Opened: 1999 |
FACP[edit | edit source]
The building is protected by a Notifier SFP-400B conventional fire alarm system. The panel is located in the main entrance. The system coding is continuous.
Notification Appliances[edit | edit source]
All notification appliances are Wheelock MB-G6-24 motor bells (6” gong) mounted on Wheelock RSSP-2415W strobe plates (red, 15cd).
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are Notifier NFM-950B conventional single-action pull stations.
Automatic Detection Devices[edit | edit source]
There are System Sensor “i3” C2W-BA conventional photoelectric smoke detectors throughout.
EOLs[edit | edit source]
There are Notifier EOL-CR end-of-line resistor plates on all circuits.
System Specifications (First Nations House) (1999-present)[edit | edit source]
System Specifications |
---|
FACP: Notifier SFP-400B FACP Location: Main Entrance Vestibule System Type: Single-Stage Conventional System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Continuous Strobes Synchronized: No Date of last known Upgrade: N/A Year Opened: 1999 |
FACP[edit | edit source]
The building is protected by a Notifier SFP-400B conventional fire alarm system. The panel is located in the main entrance. The system coding is continuous.
Notification Appliances[edit | edit source]
All notification appliances are Wheelock MB-G6-24 motor bells (6” gong) mounted on Wheelock RSSP-2415W strobe plates (red, 15cd).
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are Notifier NFM-950B conventional single-action pull stations.
Automatic Detection Devices[edit | edit source]
There are System Sensor “i3” C2W-BA conventional photoelectric smoke detectors throughout.
EOLs[edit | edit source]
There are Notifier EOL-CR end-of-line resistor plates on all circuits.
System Specifications (Great Bear House) (1999-present)[edit | edit source]
System Specifications |
---|
FACP: Notifier SFP-400B FACP Location: Main Entrance Vestibule System Type: Single-Stage Conventional System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Continuous Strobes Synchronized: No Date of last known Upgrade: N/A Year Opened: 1999 |
FACP[edit | edit source]
The building is protected by a Notifier SFP-400B conventional fire alarm system. The panel is located in the main entrance. The system coding is continuous.
Notification Appliances[edit | edit source]
All notification appliances are Wheelock MB-G6-24 motor bells (6” gong) mounted on Wheelock RSSP-2415W strobe plates (red, 15cd).
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are Notifier NFM-950B conventional single-action pull stations.
Automatic Detection Devices[edit | edit source]
There are System Sensor “i3” C2W-BA conventional photoelectric smoke detectors throughout.
EOLs[edit | edit source]
There are Notifier EOL-CR end-of-line resistor plates on all circuits.
System Specifications (Red Rock House) (1999-present)[edit | edit source]
System Specifications |
---|
FACP: Notifier SFP-400B FACP Location: Main Entrance Vestibule System Type: Single-Stage Conventional System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Continuous Strobes Synchronized: No Date of last known Upgrade: N/A Year Opened: 1999 |
FACP[edit | edit source]
The building is protected by a Notifier SFP-400B conventional fire alarm system. The panel is located in the main entrance. The system coding is continuous.
Notification Appliances[edit | edit source]
All notification appliances are Wheelock MB-G6-24 motor bells (6” gong) mounted on Wheelock RSSP-2415W strobe plates (red, 15cd).
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are Notifier NFM-950B conventional single-action pull stations.
Automatic Detection Devices[edit | edit source]
There are System Sensor “i3” C2W-BA conventional photoelectric smoke detectors throughout.
EOLs[edit | edit source]
There are Notifier EOL-CR end-of-line resistor plates on all circuits.
System Specifications (Forest House) (1999-present)[edit | edit source]
System Specifications |
---|
FACP: Notifier SFP-400B FACP Location: Main Entrance Vestibule System Type: Single-Stage Conventional System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Continuous Strobes Synchronized: No Date of last known Upgrade: N/A Year Opened: 1999 |
FACP[edit | edit source]
The building is protected by a Notifier SFP-400B conventional fire alarm system. The panel is located in the main entrance. The system coding is continuous.
Notification Appliances[edit | edit source]
All notification appliances are Wheelock MB-G6-24 motor bells (6” gong) mounted on Wheelock RSSP-2415W strobe plates (red, 15cd).
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are Notifier NFM-950B conventional single-action pull stations.
Automatic Detection Devices[edit | edit source]
There are System Sensor “i3” C2W-BA conventional photoelectric smoke detectors throughout.
EOLs[edit | edit source]
There are Notifier EOL-CR end-of-line resistor plates on all circuits.
System Specifications (Fountain House) (1999-present)[edit | edit source]
System Specifications |
---|
FACP: Notifier SFP-400B FACP Location: Main Entrance Vestibule System Type: Single-Stage Conventional System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Continuous Strobes Synchronized: No Date of last known Upgrade: N/A Year Opened: 1999 |
FACP[edit | edit source]
The building is protected by a Notifier SFP-400B conventional fire alarm system. The panel is located in the main entrance. The system coding is continuous.
Notification Appliances[edit | edit source]
All notification appliances are Wheelock MB-G6-24 motor bells (6” gong) mounted on Wheelock RSSP-2415W strobe plates (red, 15cd).
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are Notifier NFM-950B conventional single-action pull stations.
Automatic Detection Devices[edit | edit source]
There are System Sensor “i3” C2W-BA conventional photoelectric smoke detectors throughout.
EOLs[edit | edit source]
There are Notifier EOL-CR end-of-line resistor plates on all circuits.
System Specifications (Lake House House) (1999-present)[edit | edit source]
System Specifications |
---|
FACP: Notifier SFP-400B FACP Location: Main Entrance Vestibule System Type: Single-Stage Conventional System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Continuous Strobes Synchronized: No Date of last known Upgrade: N/A Year Opened: 1999 |
FACP[edit | edit source]
The building is protected by a Notifier SFP-400B conventional fire alarm system. The panel is located in the main entrance. The system coding is continuous.
Notification Appliances[edit | edit source]
All notification appliances are Wheelock MB-G6-24 motor bells (6” gong) mounted on Wheelock RSSP-2415W strobe plates (red, 15cd).
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are Notifier NFM-950B conventional single-action pull stations.
Automatic Detection Devices[edit | edit source]
There are System Sensor “i3” C2W-BA conventional photoelectric smoke detectors throughout.
EOLs[edit | edit source]
There are Notifier EOL-CR end-of-line resistor plates on all circuits.