Westshore Town Centre

From FireAlarmPedia
System Specifications
FACP: Edwards EST3
FACP Location: Security Office
System Type: Two-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: 20BPM (Alert)
Temporal (Alarm)
Strobes Synchronized: Yes, EST
Date of last known Upgrade: 2010
Most Recent Known Modification: N/A
Year Opened: 1984

Westshore Town Centre is a shopping mall located at 2945 Jacklin Road, in Langford, British Columbia, Canada. The mall was built in 1984, and the fire alarm system was upgraded in 2010.

System Specifications (2010-present)

FACP

The building is protected by an Edwards EST3 addressable fire alarm system. The panel is located in the security office. The system runs Edwards' Signature addressable protocol, and is configured for two-stage operation. The alert signal coding is 20BPM, and the alarm signal coding is temporal.

Annunciators

There is an Edwards EST3-6ANN annunciator at the northwest entrance, equipped with an LCDXL1 display.

Booster Panels

There are likely Edwards BPS6A 6-amp booster power supplies on the system.

Notification Appliances

Most notification appliances are Edwards 439D-10AWC vibrating bells (10" gong), mounted remotely in the main mall, and mounted on Edwards 403-5A-R strobe plates (15cd) in Winners and other areas.
Some areas of the main mall have Edwards "Durabel" 6100D vibrating bells (10" gong), remaining from the original system.

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.

Automatic Detection Devices

There are EST SIGA-PS addressable photoelectric smoke detectors in some areas.
There are EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors in some areas.
All aforementioned detectors are mounted on EST SIGA-SB bases.
There are EST "SuperDuct" SIGA-SD addressable photoelectric duct smoke detectors on all air handling units.

Modules

There are EST SIGA-CT1 addressable monitor modules supervising all kitchen suppression systems, and the sprinkler system's tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.
There are EST SIGA-CC1 addressable control modules triggering all booster panels.

EOLs

There are Edwards EOL-P1 end of line resistor plates on all kitchen suppression, sprinkler and signal circuits.