System Specifications
FACP: EST QuickStart QS1
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR (FACP)
24VDC (Boosters)
System Coding: Temporal
Strobes Synchronized: Yes, Self-Sync
Date of last known Upgrade: N/A
Year Opened: 2000

Wingate is a chain of lower-midrange hotels owned by Wyndham. They have locations in several countries, and are headquartered in Parsippany, New Jersey. This particular hotel is located at 20 Stafford Dr S, Lethbridge, AB. The hotel opened in 2000 as a Holiday Inn Express, but became a Wingate property in 2020, following the opening of a brand new Holiday Inn Express on the South side of town. The fire alarm system is mostly original.

System Specifications

Fire Alarmpedia apologizes for the previous inaccuracies this page contained.

FACP

The building is protected by an EST QuickStart QS1 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs EST's Signature addressable protocol, and the system coding is temporal.
This panel replaced an Edwards EST2 in the late 2000s, and is GE-EST branded.

Annunciators

There is an Edwards EST-SRA4 annunciator in the south entrance vestibule.

Booster Panels

There are likely several Edwards BPS6AC 6-amp booster power supplies on the system due to the presence of insuite devices.

Notification Appliances

Common Areas

All public areas of the hotel have General Signal MB10-24 motor bells (10” gong) on Edwards 403-5A-R strobe plates (15cd).
Some areas have Edwards MB10-24 motor bells (10" gong) as deficiency replacements.

Guest Rooms

The guest rooms have General Signal 683-1CR silenceable mini-horns (red) paired with Edwards 202-5A-T remote strobes (red, 15cd).
Some rooms have Edwards 683-1C silenceable mini-horns (white) as deficiency replacements.
Handicap room bathrooms have Mircom "Select-A-Strobe" FS-240R remote strobes (red, wall-mount, set to 15cd).

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270 addressable single-action pull stations.

Automatic Detection Devices

There are EST SIGA-PS addressable photoelectric smoke detectors throughout all corridors, at the top of each stairwell, and in the breakfast area, with Edwards SIGA-OSD addressable optical smoke detectors installed as deficiency replacements.
There are EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors in some areas, such as the hotel's convenience store.
All detectors are mounted on EST SIGA-SB bases.

Modules

There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.

EOLs

There are Edwards EOL-P1 end-of-line resistor plates on all sprinkler and signal circuits.