More actions
No edit summary |
No edit summary |
||
(2 intermediate revisions by the same user not shown) | |||
Line 5: | Line 5: | ||
| | | | ||
|- | |- | ||
| FACP: Notifier NFS-320C <br />FACP Location: Top of | | FACP: Notifier NFS-320C <br />FACP Location: Top of West Stairwell <br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal <br>Strobes Synchronized: Yes, System Sensor <br />Date of last known Upgrade: N/A <br />Year Opened: 2010 | ||
|} | |} | ||
'''Central Memorial Park''' is a park located in Beltline, Calgary. This page will cover the Facilities Building, located at 1221 2 St SW, Calgary, AB. It was built in 2010, and the fire alarm system is original. | '''Central Memorial Park''' is a park located in Beltline, Calgary. This page will cover the Facilities Building, located at 1221 2 St SW, Calgary, AB. It was built in 2010, and the fire alarm system is original. | ||
==System Specifications== | ==System Specifications== | ||
====FACP==== | ====FACP==== | ||
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located | The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located at the top of the west stairwell. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal. | ||
====Notification Appliances==== | |||
All indoor notification appliances are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd). <br>For outdoor notification, there is a System Sensor SRKA weatherproof remote strobe (red, wall-mount) outside the main entrance. | All indoor notification appliances are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd). <br>For outdoor notification, there is a System Sensor SRKA weatherproof remote strobe (red, wall-mount) outside the main entrance. | ||
===Initiating Devices=== | ===Initiating Devices=== | ||
Line 17: | Line 17: | ||
All pull stations are Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules. | All pull stations are Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules. | ||
====Automatic Detection Devices==== | ====Automatic Detection Devices==== | ||
There are Notifier FSP-851A addressable photoelectric smoke detectors in each stairwell. <br>There are Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detectors at the top of the elevator shaft and the mechanical/furnace room. <br>All aforementioned detectors are mounted on | There are Notifier FSP-851A addressable photoelectric smoke detectors in each stairwell. <br>There are Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detectors at the top of the elevator shaft and the mechanical/furnace room. <br>All aforementioned detectors are mounted on Notifier B710LPA bases. <br>There is a Notifier FSD-751PLA addressable photoelectric duct smoke detector on the main air handling unit. | ||
====Modules==== | ====Modules==== | ||
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches. <br> There | There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches. <br>There is a Notifier FRM-1A addressable relay module for HVAC shutdown. | ||
==== EOLs ==== | |||
There are Notifier EOL-CR end of line resistor plates on all signal and sprinkler circuits. | |||
[[Category:Calgary]] | [[Category:Calgary]] | ||
[[Category:Parks]] | [[Category:Parks]] |
Latest revision as of 12:27, 24 October 2024
System Specifications |
---|
FACP: Notifier NFS-320C FACP Location: Top of West Stairwell System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: N/A Year Opened: 2010 |
Central Memorial Park is a park located in Beltline, Calgary. This page will cover the Facilities Building, located at 1221 2 St SW, Calgary, AB. It was built in 2010, and the fire alarm system is original.
System Specifications[edit | edit source]
FACP[edit | edit source]
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located at the top of the west stairwell. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.
Notification Appliances[edit | edit source]
All indoor notification appliances are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd).
For outdoor notification, there is a System Sensor SRKA weatherproof remote strobe (red, wall-mount) outside the main entrance.
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules.
Automatic Detection Devices[edit | edit source]
There are Notifier FSP-851A addressable photoelectric smoke detectors in each stairwell.
There are Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detectors at the top of the elevator shaft and the mechanical/furnace room.
All aforementioned detectors are mounted on Notifier B710LPA bases.
There is a Notifier FSD-751PLA addressable photoelectric duct smoke detector on the main air handling unit.
Modules[edit | edit source]
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There is a Notifier FRM-1A addressable relay module for HVAC shutdown.
EOLs[edit | edit source]
There are Notifier EOL-CR end of line resistor plates on all signal and sprinkler circuits.