Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

Calgary Fire Department Station 22: Difference between revisions

From FireAlarmPedia
(Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Simplex 4100U <br />FACP Location: Main Entrance Vestibule <br />System Type: Single-...")
 
(Corrected some system details as there is no sprinkler system here, yet the EOLs said there was.)
 
Line 28: Line 28:
==== Automatic Detection Devices ====
==== Automatic Detection Devices ====


There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors in the living areas. <br> There are Simplex 4098-9733 addressable 135°F fixed-temperature/rate-of-rise heat detectors in the apparatus bay, kitchen, storage, electrical and mechanical rooms. <br> All detectors are mounted on Simplex 4098-9792 bases. <br> There is a Simplex 4098-9755 duct smoke detector housing on the air handling unit, with a Simplex 4098-9714 addressable photoelectric head.
There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors in the living areas. <br> There are Simplex 4098-9733 addressable 135°F fixed-temperature/rate-of-rise heat detectors in the apparatus bay, kitchen, storage, electrical and mechanical rooms. <br> All aforementioned detectors are mounted on Simplex 4098-9792 bases. <br> There is a Simplex 4098-9755 duct smoke detector housing on the air handling unit, with a Simplex 4098-9714 addressable photoelectric head.


==== Modules ====
==== Modules ====


There are Simplex 4090-9001 addressable monitor modules supervising the kitchen suppression system. <br> There are Simplex 4090-9116 isolator modules on the SLCs.
There is a Simplex 4090-9001 addressable monitor module supervising the kitchen suppression system. <br> There are Simplex 4090-9116 addressable isolator modules on the SLC.


==== EOLs ====
==== EOLs ====


There are Simplex 2081-9040C end-of-line resistor plates on all sprinkler and signal circuits.
There are Simplex 2081-9040C end-of-line resistor plates on the kitchen suppression circuit and on all signal circuits.


[[Category:Calgary]]
[[Category:Calgary]]
[[Category:Emergency Services]]
[[Category:Emergency Services]]

Latest revision as of 09:57, 15 February 2025

System Specifications
FACP: Simplex 4100U
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, SmartSync
Date of last known Upgrade: 2010
Year Opened: 1979

The Calgary Fire Department is the fire department serving The City of Calgary. This page will cover Station 22, located at 7199 Temple Dr NE, Calgary, Alberta. The station was built in 1979, and the fire alarm system was upgraded in 2010.

System Specifications (2010-present)

FACP

The building is protected by a Simplex 4100U addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Simplex’s IDNet addressable protocol, and the system coding is temporal.

Notification Appliances

All common area notification appliances are Simplex “TrueAlert” 4906-9127 horn/strobes (red, wall-mount, set to 15cd).
Some dorm rooms have Simplex 4901-9851C mini-horns (red, wall-mount, silenceable).
For exterior notification, there is a Simplex 4906-9131 weatherproof horn/strobe (red, wall-mount, set to 60cd) outside the entrance.

Initiating Devices

Pull Stations

All pull stations are Simplex 4099-9001 addressable single-action pull stations.

Automatic Detection Devices

There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors in the living areas.
There are Simplex 4098-9733 addressable 135°F fixed-temperature/rate-of-rise heat detectors in the apparatus bay, kitchen, storage, electrical and mechanical rooms.
All aforementioned detectors are mounted on Simplex 4098-9792 bases.
There is a Simplex 4098-9755 duct smoke detector housing on the air handling unit, with a Simplex 4098-9714 addressable photoelectric head.

Modules

There is a Simplex 4090-9001 addressable monitor module supervising the kitchen suppression system.
There are Simplex 4090-9116 addressable isolator modules on the SLC.

EOLs