Paradise Chalet (Marmot Basin): Difference between revisions

From FireAlarmPedia
No edit summary
No edit summary
 
(2 intermediate revisions by 2 users not shown)
Line 6: Line 6:
|  
|  
|-
|-
| FACP: Notifier System 5000 <br /> FACP Location: Main Entrance <br />System Type: Conventional <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br /> System Coding: Continuous <br />Date of last known Upgrade: N/A <br />Year Opened: 1991
| FACP: Notifier System 5000 <br />FACP Location: Main Entrance Vestibule<br />System Type: Single-Stage Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Continuous <br />Date of last known Upgrade: N/A  
Most Recent Known Modification: 2010s (Smoke Detectors)<br />Year Opened: 1991
|}
|}
'''Marmot Basin''' is an alpine ski resort located in Jasper National Park, AB. It is located 20 minutes away from Jasper. The resort has 91 ski runs, 6 chairlifts, and three daylodges. This page will cover the Paradise Chalet, which is located mid-mountain in the same building with Eagle Chalet. This daylodge was built in 1991, and the fire alarm system is original.  
'''Marmot Basin''' is an alpine ski resort located in Jasper National Park, AB. It is located 20 minutes away from Jasper. The resort has 91 ski runs, 6 chairlifts, and three daylodges. This page will cover the Paradise Chalet, which is located mid-mountain in the same building with Eagle Chalet. This daylodge was built in 1991, and the fire alarm system is original.  
Line 13: Line 14:
== System Specifications (1991-present) ==
== System Specifications (1991-present) ==
==== FACP ====
==== FACP ====
The building is protected by a Notifier System 5000 conventional fire alarm system. The panel is located in the main entrance, and has a capacity for 24 zones, 12 zones are in use. The lock on the cabinet has been busted, and is held shut with copper wire. The system coding is continuous.
The building is protected by a Notifier System 5000 conventional fire alarm system. The panel is located in the main entrance vestibule. The system coding is continuous.
==== Notification Appliances ====
All notification appliances but two are Notifier KMS-10-24VDC/P motor bells (10" gong).  


The System 5000 may be too big, but was installed likely due to supply issues.
There is a Notifier KMS-6-24VDC/P motor bell (6" gong) in the basement.  
==== Notification Appliances ====
Most notification appliances except one are Notifier KMS-10-24VDC/P motor bells (10” gong).  


In the basement, there is a Notifier KMS-6-24VDC/P motor bell (6" gong).
There is a Mircom "Select-A-Horn/Strobe" FHS-240R horn/strobe (red, wall-mount, set to 15cd) in Jim's Den.  
=== Initiating Devices ===
=== Initiating Devices ===
==== Pull Stations ====
==== Pull Stations ====
All pull stations are Notifier FM-950B conventional pull stations (black label).  
All pull stations are Notifier FM-950B conventional single-action pull stations (black label).  
==== Automatic Detection Devices ====
==== Automatic Detection Devices ====
There is a conventional duct smoke detector in the furnace room.  
There are System Sensor C2W-BA conventional photoelectric smoke detectors at the top of each stairwell.
 
There are FDD CF-200 conventional 200°F fixed-temperature heat detectors in the kitchen.
 
There is an FDD CF-135 conventional 135°F fixed-temperature heat detector in the pump room.


The rest of the building is protected by a sprinkler system with waterflow detection.
There is a System Sensor D2A conventional photoelectric duct smoke detector on the main furnace unit.


There is also a suppression system in the kitchen, wired as a conventional zone.
==== EOLs ====
There are Notifier EOL-CR end of line resistor plates on all circuits.
[[Category:Facilities]]
[[Category:Facilities]]
[[Category:Alberta]]
[[Category:Alberta]]
[[Category:Winter Sports]]
[[Category:Winter Sports]]

Latest revision as of 17:32, 4 May 2025

System Specifications
FACP: Notifier System 5000
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Continuous
Date of last known Upgrade: N/A

Most Recent Known Modification: 2010s (Smoke Detectors)
Year Opened: 1991

Marmot Basin is an alpine ski resort located in Jasper National Park, AB. It is located 20 minutes away from Jasper. The resort has 91 ski runs, 6 chairlifts, and three daylodges. This page will cover the Paradise Chalet, which is located mid-mountain in the same building with Eagle Chalet. This daylodge was built in 1991, and the fire alarm system is original.

The two lodge's fire alarm systems are NOT connected.

System Specifications (1991-present)

FACP

The building is protected by a Notifier System 5000 conventional fire alarm system. The panel is located in the main entrance vestibule. The system coding is continuous.

Notification Appliances

All notification appliances but two are Notifier KMS-10-24VDC/P motor bells (10" gong).

There is a Notifier KMS-6-24VDC/P motor bell (6" gong) in the basement.

There is a Mircom "Select-A-Horn/Strobe" FHS-240R horn/strobe (red, wall-mount, set to 15cd) in Jim's Den.

Initiating Devices

Pull Stations

All pull stations are Notifier FM-950B conventional single-action pull stations (black label).

Automatic Detection Devices

There are System Sensor C2W-BA conventional photoelectric smoke detectors at the top of each stairwell.

There are FDD CF-200 conventional 200°F fixed-temperature heat detectors in the kitchen.

There is an FDD CF-135 conventional 135°F fixed-temperature heat detector in the pump room.

There is a System Sensor D2A conventional photoelectric duct smoke detector on the main furnace unit.

EOLs

There are Notifier EOL-CR end of line resistor plates on all circuits.