'''Waterton International Hostel''' is a hostel on Cameron Falls Drive, Waterton, AB. It consists of the main building, which also houses a recreation centre, as well as nine guest houses, all built in 1999. The main building’s fire alarm system is mostly original, and all guest houses fire alarm systems are original.
'''Waterton International Hostel''' is a hostel on Cameron Falls Drive, Waterton, AB. It consists of the main building, which also houses a recreation centre, as well as nine guest houses, all built in 1999. This page will cover the main building; the fire alarm system is mostly original.


== System Specifications (Main Building) (1999-present) ==
== System Specifications (1999-present) ==


==== FACP ====
==== FACP ====
Line 34: Line 34:
There are Notifier EOL-CR end-of-line resistor plates on all circuits.
There are Notifier EOL-CR end-of-line resistor plates on all circuits.


== System Specifications (Wildflower House) (1999-present) ==
{| style="float:right;border:2px solid black"
|-
! System Specifications
|-
|
|-
| FACP: Notifier SFP-400B <br />FACP Location: Main Entrance Vestibule <br />System Type: Single-Stage Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Continuous <br>Strobes Synchronized: No  <br />Date of last known Upgrade: N/A <br />Year Opened: 1999
|}
==== FACP ====
The building is protected by a Notifier SFP-400B conventional fire alarm system. The panel is located in the main entrance. The system coding is continuous.
==== Notification Appliances ====
All notification appliances are Wheelock MB-G6-24 motor bells (6” gong) mounted on Wheelock RSSP-2415W strobe plates (red, 15cd).
=== Initiating Devices ===
==== Pull Stations ====
All pull stations are Notifier NFM-950B conventional single-action pull stations.
==== Automatic Detection Devices ====
There are System Sensor “i3” C2W-BA conventional photoelectric smoke detectors throughout.
==== EOLs ====
There are Notifier EOL-CR end-of-line resistor plates on all circuits.
== System Specifications (Mountain House) (1999-present) ==
{| style="float:right;border:2px solid black"
|-
! System Specifications
|-
|
|-
| FACP: Notifier SFP-400B <br />FACP Location: Main Entrance Vestibule <br />System Type: Single-Stage Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Continuous <br>Strobes Synchronized: No  <br />Date of last known Upgrade: N/A <br />Year Opened: 1999
|}
==== FACP ====
The building is protected by a Notifier SFP-400B conventional fire alarm system. The panel is located in the main entrance. The system coding is continuous.
==== Notification Appliances ====
All notification appliances are Wheelock MB-G6-24 motor bells (6” gong) mounted on Wheelock RSSP-2415W strobe plates (red, 15cd).
=== Initiating Devices ===
==== Pull Stations ====
All pull stations are Notifier NFM-950B conventional single-action pull stations.
==== Automatic Detection Devices ====
There are System Sensor “i3” C2W-BA conventional photoelectric smoke detectors throughout.
==== EOLs ====
There are Notifier EOL-CR end-of-line resistor plates on all circuits.
== System Specifications (First Nations House) (1999-present) ==
{| style="float:right;border:2px solid black"
|-
! System Specifications
|-
|
|-
| FACP: Notifier SFP-400B <br />FACP Location: Main Entrance Vestibule <br />System Type: Single-Stage Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Continuous <br>Strobes Synchronized: No  <br />Date of last known Upgrade: N/A <br />Year Opened: 1999
|}
==== FACP ====
The building is protected by a Notifier SFP-400B conventional fire alarm system. The panel is located in the main entrance. The system coding is continuous.
==== Notification Appliances ====
All notification appliances are Wheelock MB-G6-24 motor bells (6” gong) mounted on Wheelock RSSP-2415W strobe plates (red, 15cd).
=== Initiating Devices ===
==== Pull Stations ====
All pull stations are Notifier NFM-950B conventional single-action pull stations.
==== Automatic Detection Devices ====
There are System Sensor “i3” C2W-BA conventional photoelectric smoke detectors throughout.
==== EOLs ====
There are Notifier EOL-CR end-of-line resistor plates on all circuits.
== System Specifications (Great Bear House) (1999-present) ==
{| style="float:right;border:2px solid black"
|-
! System Specifications
|-
|
|-
| FACP: Notifier SFP-400B <br />FACP Location: Main Entrance Vestibule <br />System Type: Single-Stage Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Continuous <br>Strobes Synchronized: No  <br />Date of last known Upgrade: N/A <br />Year Opened: 1999
|}
==== FACP ====
The building is protected by a Notifier SFP-400B conventional fire alarm system. The panel is located in the main entrance. The system coding is continuous.
==== Notification Appliances ====
All notification appliances are Wheelock MB-G6-24 motor bells (6” gong) mounted on Wheelock RSSP-2415W strobe plates (red, 15cd).
=== Initiating Devices ===
==== Pull Stations ====
All pull stations are Notifier NFM-950B conventional single-action pull stations.
==== Automatic Detection Devices ====
There are System Sensor “i3” C2W-BA conventional photoelectric smoke detectors throughout.
==== EOLs ====
There are Notifier EOL-CR end-of-line resistor plates on all circuits.
== System Specifications (Red Rock House) (1999-present) ==
{| style="float:right;border:2px solid black"
|-
! System Specifications
|-
|
|-
| FACP: Notifier SFP-400B <br />FACP Location: Main Entrance Vestibule <br />System Type: Single-Stage Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Continuous <br>Strobes Synchronized: No  <br />Date of last known Upgrade: N/A <br />Year Opened: 1999
|}
==== FACP ====
The building is protected by a Notifier SFP-400B conventional fire alarm system. The panel is located in the main entrance. The system coding is continuous.
==== Notification Appliances ====
All notification appliances are Wheelock MB-G6-24 motor bells (6” gong) mounted on Wheelock RSSP-2415W strobe plates (red, 15cd).
=== Initiating Devices ===
==== Pull Stations ====
All pull stations are Notifier NFM-950B conventional single-action pull stations.
==== Automatic Detection Devices ====
There are System Sensor “i3” C2W-BA conventional photoelectric smoke detectors throughout.
==== EOLs ====
There are Notifier EOL-CR end-of-line resistor plates on all circuits.
== System Specifications (Forest House) (1999-present) ==
{| style="float:right;border:2px solid black"
|-
! System Specifications
|-
|
|-
| FACP: Notifier SFP-400B <br />FACP Location: Main Entrance Vestibule <br />System Type: Single-Stage Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Continuous <br>Strobes Synchronized: No  <br />Date of last known Upgrade: N/A <br />Year Opened: 1999
|}
==== FACP ====
The building is protected by a Notifier SFP-400B conventional fire alarm system. The panel is located in the main entrance. The system coding is continuous.
==== Notification Appliances ====
All notification appliances are Wheelock MB-G6-24 motor bells (6” gong) mounted on Wheelock RSSP-2415W strobe plates (red, 15cd).
=== Initiating Devices ===
==== Pull Stations ====
All pull stations are Notifier NFM-950B conventional single-action pull stations.
==== Automatic Detection Devices ====
There are System Sensor “i3” C2W-BA conventional photoelectric smoke detectors throughout.
==== EOLs ====
There are Notifier EOL-CR end-of-line resistor plates on all circuits.
== System Specifications (Fountain House) (1999-present) ==
{| style="float:right;border:2px solid black"
|-
! System Specifications
|-
|
|-
| FACP: Notifier SFP-400B <br />FACP Location: Main Entrance Vestibule <br />System Type: Single-Stage Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Continuous <br>Strobes Synchronized: No  <br />Date of last known Upgrade: N/A <br />Year Opened: 1999
|}
==== FACP ====
The building is protected by a Notifier SFP-400B conventional fire alarm system. The panel is located in the main entrance. The system coding is continuous.
==== Notification Appliances ====
All notification appliances are Wheelock MB-G6-24 motor bells (6” gong) mounted on Wheelock RSSP-2415W strobe plates (red, 15cd).
=== Initiating Devices ===
==== Pull Stations ====
All pull stations are Notifier NFM-950B conventional single-action pull stations.
==== Automatic Detection Devices ====
There are System Sensor “i3” C2W-BA conventional photoelectric smoke detectors throughout.
==== EOLs ====
There are Notifier EOL-CR end-of-line resistor plates on all circuits.
== System Specifications (Lake House House) (1999-present) ==
{| style="float:right;border:2px solid black"
|-
! System Specifications
|-
|
|-
| FACP: Notifier SFP-400B <br />FACP Location: Main Entrance Vestibule <br />System Type: Single-Stage Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Continuous <br>Strobes Synchronized: No  <br />Date of last known Upgrade: N/A <br />Year Opened: 1999
|}
==== FACP ====
The building is protected by a Notifier SFP-400B conventional fire alarm system. The panel is located in the main entrance. The system coding is continuous.
==== Notification Appliances ====
All notification appliances are Wheelock MB-G6-24 motor bells (6” gong) mounted on Wheelock RSSP-2415W strobe plates (red, 15cd).
=== Initiating Devices ===
==== Pull Stations ====
All pull stations are Notifier NFM-950B conventional single-action pull stations.
==== Automatic Detection Devices ====
There are System Sensor “i3” C2W-BA conventional photoelectric smoke detectors throughout.
==== EOLs ====
There are Notifier EOL-CR end-of-line resistor plates on all circuits.


[[Category:Hostels]]
[[Category:Hostels]]
[[Category:Alberta]]
[[Category:Alberta]]

Latest revision as of 22:56, 12 April 2025

System Specifications
FACP: Simplex 4007ES
FACP Location: Front Entrance
System Type: Single-Stage Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Continuous
Strobes Synchronized: No
Date of last known Upgrade: 2010s
Year Opened: 1999

Waterton International Hostel is a hostel on Cameron Falls Drive, Waterton, AB. It consists of the main building, which also houses a recreation centre, as well as nine guest houses, all built in 1999. This page will cover the main building; the fire alarm system is mostly original.

System Specifications (1999-present)

FACP

The building is protected by a Simplex 4007ES conventional fire alarm system. The panel is located at the front entrance. The system coding is continuous.
This panel replaced a Notifier System 500 in the late 2010s. There is also a Notifier System 2500, however it is unknown what this panel supervises.

Notification Appliances

All common area notification appliances are Wheelock MB-G6-24 motor bells (6” gong) mounted on Wheelock RSSP-2415W strobe plates (red, 15cd).
Each living unit has a System Sensor “SpectrAlert” S2415A remote strobe (red, wall-mount, 15cd).
For exterior notification, there is a Wheelock MB-G6-24 motor bell (6” gong) outside the entrance.

Initiating Devices

Pull Stations

Most pull stations are Notifier NFM-950B conventional single-action pull stations.
There are some Edwards 270-SPO conventional single-action pull stations.

Automatic Detection Devices

There are System Sensor 1400A conventional ionization smoke detectors in most areas.
Some areas have System Sensor “i3” C2W-BA conventional photoelectric smoke detectors.
There are Simplex “TrueAlarm” 4098-9601 conventional photoelectric smoke detectors mounted to Simplex 4098-9788 bases as deficiency replacements.
All kitchens have Edwards 281C conventional 135°F fixed-temperature/rate-of-rise heat detectors.

EOLs

There are Notifier EOL-CR end-of-line resistor plates on all circuits.