Line 7: | Line 7: | ||
| FACP: Notifier NFS-320C <br />FACP Location: Top of South Stairwell <br />System Type: Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal <br>Strobes Synchronized: Yes, SS <br />Date of last known Upgrade: N/A <br />Year Opened: 2010 | | FACP: Notifier NFS-320C <br />FACP Location: Top of South Stairwell <br />System Type: Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal <br>Strobes Synchronized: Yes, SS <br />Date of last known Upgrade: N/A <br />Year Opened: 2010 | ||
|} | |} | ||
'''Central Memorial Park''' is a park located in Beltline, Calgary. This page will cover the Facilities Building, located at 1221 2 St SW, Calgary, AB. It was built in 2010, and the fire alarm system is original. | '''Central Memorial Park''' is a park located in Beltline, Calgary. This page will cover the Facilities Building, located at 1221 2 St SW, Calgary, AB. It was built in 2010, and the fire alarm system is original. | ||
==System Specifications== | ==System Specifications== | ||
====FACP==== | ====FACP==== | ||
The building is protected by a Notifier NFS-320C addressable fire alarm system. | The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in at the top of the south stairwell. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal. | ||
=====Notification Appliances==== | =====Notification Appliances==== | ||
All indoor notification appliances are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd). | All indoor notification appliances are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd). <br>For outdoor notification, there is a System Sensor SRKA weatherproof remote strobe (red, wall-mount) outside the main entrance. | ||
===Initiating Devices=== | ===Initiating Devices=== | ||
====Pull Stations==== | ====Pull Stations==== | ||
All pull stations are Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules. | All pull stations are Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules. | ||
====Automatic Detection Devices==== | ====Automatic Detection Devices==== | ||
There are Notifier FSP-851A addressable photoelectric smoke detectors in each stairwell. | There are Notifier FSP-851A addressable photoelectric smoke detectors in each stairwell. <br>There are Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detectors at the top of the elevator shaft and the mechanical/furnace room. <br>All aforementioned detectors are mounted on System Sensor B710LPA bases. <br>There is a System Sensor DNRA addressable duct detector housing with an FSP-851A addressable photoelectric smoke detector head on the make-up air unit. | ||
====Modules==== | ====Modules==== | ||
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches. <br> There are Notifier FRM-1A addressable relays for HVAC shutdown. | There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches. <br> There are Notifier FRM-1A addressable relays for HVAC shutdown. | ||
[[Category:Calgary]] | |||
[[Category:Parks]] |
Revision as of 19:08, 23 May 2024
System Specifications |
---|
FACP: Notifier NFS-320C FACP Location: Top of South Stairwell System Type: Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, SS Date of last known Upgrade: N/A Year Opened: 2010 |
Central Memorial Park is a park located in Beltline, Calgary. This page will cover the Facilities Building, located at 1221 2 St SW, Calgary, AB. It was built in 2010, and the fire alarm system is original.
System Specifications
FACP
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in at the top of the south stairwell. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.
=Notification Appliances
All indoor notification appliances are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd).
For outdoor notification, there is a System Sensor SRKA weatherproof remote strobe (red, wall-mount) outside the main entrance.
Initiating Devices
Pull Stations
All pull stations are Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules.
Automatic Detection Devices
There are Notifier FSP-851A addressable photoelectric smoke detectors in each stairwell.
There are Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detectors at the top of the elevator shaft and the mechanical/furnace room.
All aforementioned detectors are mounted on System Sensor B710LPA bases.
There is a System Sensor DNRA addressable duct detector housing with an FSP-851A addressable photoelectric smoke detector head on the make-up air unit.
Modules
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Notifier FRM-1A addressable relays for HVAC shutdown.