More actions
No edit summary |
|||
Line 15: | Line 15: | ||
=== Initiating Devices === | === Initiating Devices === | ||
==== Pull Stations ==== | ==== Pull Stations ==== | ||
Most pull stations are Simplex 2099-9795 addressable single-action pull stations, converted to conventional <br> There is an Edwards 270-SPOW conventional single-action pull station in the pool area. <br> There is a Fire-Lite MPS-950BF conventional pull station at the main entrance as a deficiency replacement. <br> All above pull stations are wired to Mircom MIX-M501MA addressable monitor modules. <br> There is a Mircom MS-401AP addressable single-action pull station at the east exit as a deficiency replacement. | Most pull stations are Simplex 2099-9795 addressable single-action pull stations, converted to conventional. <br> There is an Edwards 270-SPOW conventional single-action pull station in the pool area. <br> There is a Fire-Lite MPS-950BF conventional pull station at the main entrance as a deficiency replacement. <br> All above pull stations are wired to Mircom MIX-M501MA addressable monitor modules. <br> There is a Mircom MS-401AP addressable single-action pull station at the east exit as a deficiency replacement. | ||
==== Automatic Detection Devices ==== | ==== Automatic Detection Devices ==== | ||
There are Mircom MIX-2251BA addressable photoelectric smoke detectors at the top of each stairwell. <br> There are Mircom MIX-2251RBA addressable 135°F fixed temperature heat detectors throughout the building. <br> In areas with higher ambient temperatures, there are Mircom MIX-5251HBA addressable 135°F fixed temperature heat detectors <br> All above detectors are mounted on System Sensor B710LPA bases. <br> There is a Mircom MIX-5351RAPA addressable 135°F fixed-temperature/rate of rise heat detector in the mechanical room, mounted on a System Sensor B300A-6 base as a deficiency replacement. | There are Mircom MIX-2251BA addressable photoelectric smoke detectors at the top of each stairwell. <br> There are Mircom MIX-2251RBA addressable 135°F fixed temperature heat detectors throughout the building. <br> In areas with higher ambient temperatures, there are Mircom MIX-5251HBA addressable 135°F fixed temperature heat detectors <br> All above detectors are mounted on System Sensor B710LPA bases. <br> There is a Mircom MIX-5351RAPA addressable 135°F fixed-temperature/rate of rise heat detector in the mechanical room, mounted on a System Sensor B300A-6 base as a deficiency replacement. |
Revision as of 09:40, 9 June 2024
System Specifications |
---|
FACP: Mircom FX-2000 FACP Location: Main Entrance Vestibule System Type: Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Continuous Strobes Synchronized: No Date of last known Upgrade: 2010s Year Opened: 1970 |
Bob Bahan Aquatic & Fitness Centre is a now closed swimming pool & fitness centre located at 4812 14 Ave SE, Calgary, AB. It is owned and operated by the City of Calgary. The facility was built in 1970, and underwent a major renovation between 1999 and 2000. The fire alarm system was upgraded in 2000, and again in 2006.
System Specifications (2006-present)
FACP
The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Mircom’s CLIP addressable protocol, and the system coding is continuous.
The FX-2000 replaced a Simplex 4020 as part of an upgrade project for select buildings.
Notification Appliances
Most notification appliances are Simplex 2901-9723 motor bells (6” gong) mounted on Wheelock RSSP-2415W-FR strobe plates (red, 15cd).
There are Mircom BL-10B motor bells (10” gong) mounted on Wheelock RSSP-24MCW-FR strobe plates (red, set to 15cd) as deficiency replacements in some areas.
There is an Edwards 439D-6AWC vibrating bell (6” gong) mounted on an EST “Integrity” 403-5A-R strobe plate (15cd) in the basement mechanical room, also a deficiency replacement.
Initiating Devices
Pull Stations
Most pull stations are Simplex 2099-9795 addressable single-action pull stations, converted to conventional.
There is an Edwards 270-SPOW conventional single-action pull station in the pool area.
There is a Fire-Lite MPS-950BF conventional pull station at the main entrance as a deficiency replacement.
All above pull stations are wired to Mircom MIX-M501MA addressable monitor modules.
There is a Mircom MS-401AP addressable single-action pull station at the east exit as a deficiency replacement.
Automatic Detection Devices
There are Mircom MIX-2251BA addressable photoelectric smoke detectors at the top of each stairwell.
There are Mircom MIX-2251RBA addressable 135°F fixed temperature heat detectors throughout the building.
In areas with higher ambient temperatures, there are Mircom MIX-5251HBA addressable 135°F fixed temperature heat detectors
All above detectors are mounted on System Sensor B710LPA bases.
There is a Mircom MIX-5351RAPA addressable 135°F fixed-temperature/rate of rise heat detector in the mechanical room, mounted on a System Sensor B300A-6 base as a deficiency replacement.