| FACP: Edwards EST3X <br />FACP Location: Parkade Mechanical Room <br />System Type: Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal <br>Strobes Synchronized: Yes, Genesis <br />Date of last known Upgrade: 2022 <br | | FACP: Edwards EST3X <br />FACP Location: Parkade Mechanical Room <br />System Type: Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal <br>Strobes Synchronized: Yes, Genesis <br />Date of last known Upgrade: 2022 <br>Year Opened: 2021 (1130) br> 2022 (1126) | ||
|} | |} | ||
'''The Circle at Seton''' is a group of apartment buildings located on Seton Circle SE, Calgary. This page will cover buildings 1126 and 1130, located at 1126 and 1130 Seton Circle SE, Calgary, AB, respectively. The 1130 building was built in 2021, followed by 1126 in 2022. The two buildings share a fire alarm system, and the system is original. | '''The Circle at Seton''' is a group of apartment buildings located on Seton Circle SE, Calgary. This page will cover buildings 1126 and 1130, located at 1126 and 1130 Seton Circle SE, Calgary, AB, respectively. The 1130 building was built in 2021, followed by 1126 in 2022. The two buildings share a fire alarm system, and the system is original. |
Revision as of 00:24, 22 September 2024
System Specifications |
---|
FACP: Edwards EST3X FACP Location: Parkade Mechanical Room System Type: Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, Genesis Date of last known Upgrade: 2022 Year Opened: 2021 (1130) br> 2022 (1126) |
The Circle at Seton is a group of apartment buildings located on Seton Circle SE, Calgary. This page will cover buildings 1126 and 1130, located at 1126 and 1130 Seton Circle SE, Calgary, AB, respectively. The 1130 building was built in 2021, followed by 1126 in 2022. The two buildings share a fire alarm system, and the system is original.
System Specifications (2021-present)
FACP
The buildings are protected by an Edwards EST3X addressable fire alarm system. The panel is located in the parkade mechanical room. The system runs Edwards’ Signature addressable protocol, and the system coding is temporal.
Booster Panels
There are EST APS10A 10-amp power supplies located in electrical rooms on each floor.
Annunciators
There are two sets of EST RLCD-C LCD annunciators paired with EST RLED24 LED annunciators in each entrance vestibule, mounted in RA-ENC2 enclosures.
Notification Appliances
Most notification appliances are from Edwards’ “Genesis LED” line of products.
The parkade and the corridors of building 1130 have Edwards G1AVRN horn/strobes (red, wall-mount, no marking, set to 15cd).
Some areas of the parkade have Edwards G1VRN remote strobes (red, wall-mount, no marking, set to 15cd).
The corridors of building 1126 have Edwards G1AVWN horn/strobes (white, wall-mount, no marking, set to 15cd).
Each suite has an Edwards G1VWF remote strobe (white, wall-mount, no marking, set to 110cd) in the living areas, and an Edwards 683-1C mini-horn (white, silenceable) in each bedroom.
For exterior notification, there is an Edwards CS405-7A-T weatherproof remote strobe (red, 15/75cd) outside the entrance of 1130.
Initiating Devices
Pull Stations
All pull stations are EST SIGA-270 addressable single-action pull stations.
Automatic Detection Devices
There are Edwards SIGA-OSD addressable optical smoke detectors throughout the corridors and in the elevator shafts, mounted on SIGA-SB bases.
The mechanical room has an Edwards SIGA-COD addressable carbon monoxide detector, mounted on a SIGA-AB4G sounder base, which sounds in temporal 4-4 when activated.
There are EST SIGA-SD addressable photoelectric duct smoke detectors on each building’s make-up air unit.
Modules
There are EST SIGA-CT2 addressable dual-input monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Edwards SIGA-CR addressable relay modules for HVAC shutdown and elevator recall.
Each SLC has an Edwards SIGA-IM isolator module.