Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

Mail is now working! Feel free to request an account. Accounts are available to invested enthusiasts/technicians in the industry. :)

Kilmorey Lodge: Difference between revisions

From FireAlarmPedia
(Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Simplex 4007ES <br />FACP Location: Main Entrance Vestibule <br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal <br>Strobes Synchronized: Yes, SmartSync <br />Date of last known Upgrade: N/A <br />Year Opened: 2022 |} The '''Kilmorey Lodge''' is a hotel located at 117 Evergreen Ave, in Waterton Park, Al...")
 
No edit summary
Tags: Reverted Visual edit
Line 8: Line 8:
|}
|}


The '''Kilmorey Lodge''' is a hotel located at 117 Evergreen Ave, in Waterton Park, Alberta, Canada.  The lodge was originally built in 1926, and was destroyed in a fire in 2009.  This page will cover the replacement building, built in 2022.  The fire alarm system is original.
The '''Kilmorey Lodge''' is a hotel located at 117 Evergreen Ave, in Waterton Park, Alberta, Canada.  The lodge was originally built in 1926, and was destroyed in a fire in 2009.  This page will cover the replacement building, built in 2022.  The fire alarm system is original.  I wish this building would be destroyed by a fire too.  Fuck Simplex.


==System Specifications==
==System Specifications==

Revision as of 19:59, 16 December 2025

System Specifications
FACP: Simplex 4007ES
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, SmartSync
Date of last known Upgrade: N/A
Year Opened: 2022

The Kilmorey Lodge is a hotel located at 117 Evergreen Ave, in Waterton Park, Alberta, Canada. The lodge was originally built in 1926, and was destroyed in a fire in 2009. This page will cover the replacement building, built in 2022. The fire alarm system is original. I wish this building would be destroyed by a fire too. Fuck Simplex.

System Specifications

FACP

The building is protected by a Simplex 4007ES addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Simplex’s IDNet addressable protocol, and the system coding is temporal.

Notification Appliances

Most common areas have Simplex “TrueAlert” 4906-9128 horn/strobes (red, ceiling-mount, set to 15cd).
All other areas, including guest rooms, have Simplex 4906-9127 horn/strobes (red, wall-mount, set to 15cd).

Initiating Devices

Pull Stations

All pull stations are Simplex 4099-9004 addressable single-action pull stations.

Automatic Detection Devices

There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors throughout all areas, including guest rooms, mounted on Simplex 4098-9792 bases.

Modules

There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Simplex 4090-9002 addressable relay modules serving various purposes.
There are Simplex 4090-9116 addressable isolator modules on the SLC.

EOLs

There are Simplex 2081-9040C end of line resistor plates on all sprinkler and signal circuits.