Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

Beaumont Community Centre: Difference between revisions

From FireAlarmPedia
(Added categories and corrected panel model. The iO cannot do two-stage.)
(FUCK YOUR FWR)
Line 5: Line 5:
|  
|  
|-
|-
| FACP: Edwards EST3X?<br />FACP Location: Unknown <br />System Type: Addressable (Two-Stage) <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: 20BPM (Alert) <br> Temporal (Alarm) <br>Strobes Synchronized: Yes, EST <br />Date of last known Upgrade: N/A <br />Year Opened: 2015
| FACP: Edwards EST3X?<br />FACP Location: Unknown <br />System Type: Addressable (Two-Stage) <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC<br />System Coding: 20BPM (Alert) <br> Temporal (Alarm) <br>Strobes Synchronized: Yes, EST <br />Date of last known Upgrade: N/A <br />Year Opened: 2015
|}
|}
The '''Beaumont Community Centre''' is a community centre located at 5204 50 Ave, Beaumont, AB. It spans two floors, has an area of 30,000 sq ft, has the largest banquet facility in Leduc County, and a seating capacity for 500. It was built in 2015, and the fire alarm system is original.  
The '''Beaumont Community Centre''' is a community centre located at 5204 50 Ave, Beaumont, AB. It spans two floors, has an area of 30,000 sq ft, has the largest banquet facility in Leduc County, and a seating capacity for 500. It was built in 2015, and the fire alarm system is original.  
== System Specifications (2015-present) ==
== System Specifications (2015-present) ==
Please note that the FACP model is unconfirmed. This page should not be used for official purposes.
Please note that the FACP model is unconfirmed. This page should not be used for official purposes.
 
==== FACP ====
==== FACP ====
The building is protected by an Edwards EST3X addressable fire alarm system. The panel location is unknown, and the model is unconfirmed. The system runs EST’s Signature addressable protocol, and is configured for two-stage operation. Alert signal coding is 20BPM, followed by temporal for the evacuation signal. General alarm timer length is 5 minutes.
The building is protected by an Edwards EST3X addressable fire alarm system. The panel location is unknown, and the model is unconfirmed. The system runs EST’s Signature addressable protocol, and is configured for two-stage operation. Alert signal coding is 20BPM, followed by temporal for the evacuation signal. General alarm timer length is 5 minutes.

Revision as of 16:42, 22 May 2024

System Specifications
FACP: Edwards EST3X?
FACP Location: Unknown
System Type: Addressable (Two-Stage)
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: 20BPM (Alert)
Temporal (Alarm)
Strobes Synchronized: Yes, EST
Date of last known Upgrade: N/A
Year Opened: 2015

The Beaumont Community Centre is a community centre located at 5204 50 Ave, Beaumont, AB. It spans two floors, has an area of 30,000 sq ft, has the largest banquet facility in Leduc County, and a seating capacity for 500. It was built in 2015, and the fire alarm system is original.

System Specifications (2015-present)

Please note that the FACP model is unconfirmed. This page should not be used for official purposes.

FACP

The building is protected by an Edwards EST3X addressable fire alarm system. The panel location is unknown, and the model is unconfirmed. The system runs EST’s Signature addressable protocol, and is configured for two-stage operation. Alert signal coding is 20BPM, followed by temporal for the evacuation signal. General alarm timer length is 5 minutes.

Annunciators

There is an EST RLCD-C LCD annunciator and an RLED24 LED annunciator in an RA-ENC2 cabinet located in the west entrance.

Notification Appliances

All notification appliances are EST “Genesis” G1F-HDVM horn/strobes (white, wall-mount, FIRE lettering, set to 15cd).

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270P addressable two-stage pull stations.

Automatic Detection Devices

There are no visible detectors, a sprinkler system with waterflow detection is present.

Modules

There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.