Central Memorial Park Facilities Building

From FireAlarmPedia
Revision as of 16:22, 23 September 2024 by TwentyThree33 (talk | contribs)
System Specifications
FACP: Notifier NFS-320C
FACP Location: Top of West Stairwell
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: N/A
Year Opened: 2010

Central Memorial Park is a park located in Beltline, Calgary. This page will cover the Facilities Building, located at 1221 2 St SW, Calgary, AB. It was built in 2010, and the fire alarm system is original.

System Specifications

FACP

The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located at the top of the west stairwell. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.

Notification Appliances

All indoor notification appliances are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd).
For outdoor notification, there is a System Sensor SRKA weatherproof remote strobe (red, wall-mount) outside the main entrance.

Initiating Devices

Pull Stations

All pull stations are Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules.

Automatic Detection Devices

There are Notifier FSP-851A addressable photoelectric smoke detectors in each stairwell.
There are Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detectors at the top of the elevator shaft and the mechanical/furnace room.
All aforementioned detectors are mounted on System Sensor B710LPA bases.
There is a Notifier FSD-751PLA addressable photoelectric duct smoke detector on the main air handling unit.

Modules

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There is a Notifier FRM-1A addressable relay module for HVAC shutdown.

EOLs

There are Notifier EOL-CR end of line resistor plates on all signal and sprinkler circuits.