Lincoln Park Centre

From FireAlarmPedia
Revision as of 00:46, 29 December 2024 by Alberta Fire Alarms (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Notifier NFS-320C <br />FACP Location: Main Entrance Vestibule <br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal <br>Strobes Synchronized: Yes, System Sensor <br />Date of last known Upgrade: 2023 <br />Year Opened: 2008 |} '''Lincoln Park Centre''' is a medical and professional office building locate...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Notifier NFS-320C
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: 2023
Year Opened: 2008

Lincoln Park Centre is a medical and professional office building located at 5 Richard Way SW, Calgary, AB. The building was completed in 2008 and the fire alarm system is mostly original, with a third floor upgrade taking place in 2023.

System Specifications (2008-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.

Booster Panels[edit | edit source]

There are two Notifier FCPS-24S8C 8-amp booster power supplies on the system. One is located above the ceiling in the north hallway, and the other is in the third floor tenant electrical room.

Notification Appliances[edit | edit source]

Most notification appliances on the first two floors are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd).
The third floor has System Sensor “L-Series” P2RLA horn/strobes (red, wall-mount, set to 15cd/electromechanical), as well as System Sensor PC2RLA horn/strobes (red, wall-mount, set to 15cd/electromechanical); the former can also be found as deficiency replacements.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules.

Automatic Detection Devices[edit | edit source]

There are Notifier FSP-851A addressable photoelectric smoke detectors in the stairwells and elevator lobbies.
The electrical closets have Notifier FST-851A addressable 135°F fixed-temperature heat detectors.
There are Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detectors in the elevator shafts.
The main electrical room has a Notifier FST-851HA addressable 190°F fixed-temperature heat detector.
All above detectors are mounted on Notifier B710LPA bases.
The air handling units have Notifier FSD-751PLA addressable photoelectric duct smoke detectors.

Modules[edit | edit source]

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on the SLC.

EOLs[edit | edit source]

There are Notifier EOL-CR end-of-line resistor plates on all sprinkler and signal circuits.