Revision as of 13:52, 4 August 2025 by TwentyThree33 (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Edwards EST3<br />FACP Location: Fire Control Room<br />System Type: Two-Stage Addressable<br />System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (Audible)<br>24VDC (Visual)<br />System Coding: 20BPM Tone (Alert)<br>Temporal Tone (Alarm)<br>Strobes Synchronized: Yes, Genesis<br />Date of last known Upgrade: N/A<br />Most Recent Known Modification: N/A<br />Year Opened: 2010 |}...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Edwards EST3
FACP Location: Fire Control Room
System Type: Two-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 70.7VRMS (Audible)
24VDC (Visual)
System Coding: 20BPM Tone (Alert)
Temporal Tone (Alarm)
Strobes Synchronized: Yes, Genesis
Date of last known Upgrade: N/A
Most Recent Known Modification: N/A
Year Opened: 2010


Carewest Garrison Green is a senior living facility located at 3108 Don Ethell Blvd SW, in Calgary, Alberta, Canada. The facility is owned and operated by Alberta Health Services. The building was built in 2010, and the fire alarm system is original.


System Specifications

FACP

The building is protected by an Edwards EST3 addressable fire alarm system. The panel is located in the fire control room. The system runs Edwards’ Signature addressable protocol, is equipped with voice evacuation, and is configured for two-stage operation. The alert signal is a 20BPM tone, and the alarm signal is a temporal tone. Live “CODE RED” announcements are made by site personnel in lieu of pre-recorded messages.


Annunciators

There are Edwards EST3-LCDANN annunciators equipped with LCDXL1 displays at each nurse’s station, in the main entrance vestibule, behind the front desk, and at the main floor rear entrance.


Notification Appliances

All aboveground notification appliances are Edwards “Genesis” GC-S7VM speaker/strobes (white, ceiling-mount, no marking, 70V, set to 15cd).
The parkade has Edwards G4-S7VM speaker/strobes (white, wall-mount, no marking, 70V, set to 15cd).
For outdoor notification, there is an Edwards CS405-7A-T weatherproof remote strobe (red, 15/75cd) outside the rear entrance.


Initiating Devices

Pull Stations

All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.


Automatic Detection Devices

There are EST SIGA-PHS addressable photoelectric smoke/135°F fixed-temperature heat detectors throughout all common areas and corridors, in each patient room and in all electrical rooms.
There are EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors in the kitchen, maintenance shop and boiler room.
All aforementioned detectors are mounted on EST SIGA-SB bases.
There are EST “SuperDuct” SIGA-SD addressable photoelectric duct smoke detectors on all air handling units.


Modules

There are EST SIGA-CT1 addressable monitor modules supervising the kitchen suppression system, the generator’s run/trouble contacts, and the sprinkler system’s tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.
There are EST SIGA-IM addressable isolator modules on all SLCs.


EOLs

There are Edwards EOL-P1 end of line resistor plates on all circuits supervised by monitor modules, and on all signal circuits.