Carewest Sarcee

From FireAlarmPedia
Revision as of 13:52, 4 August 2025 by TwentyThree33 (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Edwards EST3<br />FACP Location: Main Telephone Room<br />System Type: Two-Stage Addressable<br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC<br />System Coding: 20BPM (Alert)<br>120BPM (Alarm)<br>Strobes Synchronized: No<br />Date of last known Upgrade: 1996<br />Most Recent Known Modification: N/A<br />Year Opened: 1960, 1976 |} '''Carewest Sarcee'''’ is a senior living...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Edwards EST3
FACP Location: Main Telephone Room
System Type: Two-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: 20BPM (Alert)
120BPM (Alarm)
Strobes Synchronized: No
Date of last known Upgrade: 1996
Most Recent Known Modification: N/A
Year Opened: 1960, 1976

Carewest Sarcee’ is a senior living facility located at 3504 Sarcee Road SW, in Calgary, Alberta, Canada. The facility is owned and operated by Alberta Health Services. The building was built in 1960, expanded in 1976, and was renovated in 1996. The fire alarm system was upgraded as part of the 1996 renovation.


System Specifications (1996-present)

Please note that this system is in the process of being upgraded.

FACP

The building is protected by an Edwards EST3 addressable fire alarm system. The panel is located in the main telephone room. The system runs Edwards’ Signature addressable protocol, and is configured for two-stage operation. The alert signal coding is 20BPM, and the alarm signal coding is 120BPM march time.


Annunciators

There are Edwards EST3-LCDANN annunciators at each nurse’s station, and in the main entrance vestibule.


Notification Appliances

All notification appliances are Edwards 439D-6AWC vibrating bells (6” gong) mounted on Edwards 403-5A-R strobe plates (15cd, unenhanced).


Initiating Devices

Pull Stations

All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.


Automatic Detection Devices

There are EST SIGA-IPHS addressable ionization/photoelectric smoke and 135°F fixed-temperature heat detectors throughout all corridors, in all patient rooms, at the top of each stairwell, and in various other areas.
There are EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors in the kitchen and in all mechanical rooms.
All aforementioned detectors are mounted on EST SIGA-SB bases.
There are EST SIGA-DH duct smoke detector housings equipped with EST SIGA-PS addressable photoelectric heads on all air handling units.


Modules

There are EST SIGA-CT1 addressable monitor modules supervising the kitchen suppression system, the generator’s run/trouble contacts, and the sprinkler system’s tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.
There are EST SIGA-IM addressable isolator modules on all SLCs.


EOLs

There are Edwards EOL-P1 end of line resistor plates on all circuits supervised by monitor modules, and on all signal circuits.