Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

Deerfoot Atria South

From FireAlarmPedia
Revision as of 20:08, 3 September 2025 by Alberta Fire Alarms (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: EST QuickStart QS4<br />FACP Location: Main Electrical Room<br />System Type: Single-Stage Addressable<br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC<br />System Coding: Temporal<br>Strobes Synchronized: Yes, Self-Sync<br />Date of last known Upgrade: 2006<br />Most Recent Known Modification: N/A<br />Year Opened: 1980 |} '''Deerfoot Atria South''' is an office building l...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: EST QuickStart QS4
FACP Location: Main Electrical Room
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, Self-Sync
Date of last known Upgrade: 2006
Most Recent Known Modification: N/A
Year Opened: 1980

Deerfoot Atria South is an office building located at 6715 8 St NE, in Calgary, Alberta, Canada. The building is owned and operated by Groupthree Property Management. The building was built in 1980, and the fire alarm system was upgraded in 2006.

System Specifications (2006-present)

FACP

The building is protected by an EST QuickStart QS4 addressable fire alarm system. The panel is located in the main electrical/fire control room on the P1 level. The system runs EST's Signature addressable protocol, and the system coding is temporal. The panel's onboard NACs are not utilized; all notification appliances are powered off booster panels.

Annunciators

There is an EST QSA-2-S annunciator in the main entrance vestibule.

Booster Panels

There are Edwards BPS6AC 6-amp booster power supplies in the main electrical room and in some other areas.

Notification Appliances

Most notification appliances are Edwards "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd).
Some areas have Edwards GC-HDVM horn/strobes (white, ceiling-mount, no marking, set to 15cd).
Some areas have Edwards G4AVRF horn/strobes (red, wall-mount, FIRE marking, set to 15cd) as deficiency replacements.

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270 addressable single-action pull stations.

Automatic Detection Devices

There are EST SIGA-PS addressable photoelectric smoke detectors in all electrical and telephone rooms, at the top of each stairwell, and in some other areas.
There are EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors in all mechanical rooms and elevator pits.
All detectors are mounted on EST SIGA-SB bases.

Modules

There are EST SIGA-CT1 addressable monitor modules supervising the generator's run and trouble contacts, and the sprinkler system's tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.

EOLs

There are Edwards EOL-P1 end of line resistor plates on all circuits supervised by monitor modules, and on all signal circuits.