| System Specifications |
|---|
| FACP: Simplex 4010ES FACP Location: Main Electrical Room System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 29VDC System Coding: Temporal Strobes Synchronized: Yes, IDNAC Date of last known Upgrade: 2010s Most Recent Known Modification: N/A Year Opened: 1914 |
CPKC is a railway headquartered in Calgary, Alberta. This page will cover Building 4 of the Ogden Campus, also known as the 1881 Lodge. The building is the main hotel for CPKC employees, and is located at 7550 Ogden Dale Road SE, in Calgary, Alberta, Canada. The building was built in 1914, and was extensively renovated in the 2010s. The fire alarm system was upgraded as part of the 2010s renovation.
System Specifications (2010s-present)
FACP
The building is protected by a Simplex 4010ES addressable fire alarm system. The panel is located in the main electrical room. The system runs Simplex's IDNet addressable initiating and IDNAC addressable indicating protocols, and the system coding is temporal.
Annunciators
There is a Simplex 4606-9102 annunciator paired with a Simplex 4602-9101 annunciator at the main entrance.
Booster Panels
There is a Simplex 4009 IDNAC repeater below the main FACP.
Notification Appliances
All indoor notification appliances are Simplex "TrueAlert ES" 49AV-WWF addressable horn/strobes (white, wall-mount, set to 15cd via FACP).
For outdoor notification, there is a Simplex 49VO-WRFO-C addressable weatherproof remote strobe (red, wall-mount) outside the main entrance.
Initiating Devices
Pull Stations
All pull stations are Simplex 4099-9004 addressable single-action pull stations.
Automatic Detection Devices
There are Simplex "TrueAlarm" 4098-9714 addressable photoelectric smoke detectors in all guest rooms, throughout all corridors, in all housekeeping rooms, throughout the lobby, and in all electrical, data and mechanical rooms.
There are Simplex 4098-9733 addressable 135°F fixed-temperature/rate-of-rise heat detectors in all janitor and food prep closets.
All guest room detectors are mounted on Simplex 4098-9794 isolator bases, while all other detectors are mounted on Simplex 4098-9792 bases.
Modules
There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are Simplex 4090-9002 addressable relay modules for AHU shutdown.
There are Simplex 4090-9116 isolator modules on the SLC.
EOLs
There are Simplex 2081-9040C end of line resistor plates on all sprinkler circuits.