Revision as of 15:22, 6 March 2026 by TwentyThree33 (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Notifier NFS2-640C<br />FACP Location: Arena 2 Main Lobby<br />System Type: Single-Stage Hybrid-Addressable<br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC<br />System Coding: Temporal<br>Strobes Synchronized: Yes, System Sensor<br />Date of last known Upgrade: N/A<br />Most Recent Known Modification: N/A<br />Year Opened: 1980s, 2021 |} '''Eagle Builders Centre''' is a re...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Notifier NFS2-640C
FACP Location: Arena 2 Main Lobby
System Type: Single-Stage Hybrid-Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: N/A
Most Recent Known Modification: N/A
Year Opened: 1980s, 2021

Eagle Builders Centre is a recreation complex located at 5302 Broadway Ave, in Blackfalds, Alberta, Canada. The complex consists of two arenas and a library; Arena 2 was built in the 1980s, and Arena 1 and the library were built in 2021. Arena 1 is home to the Blackfalds Bulldogs of the British Columbia Hockey League (BCHL). The fire alarm system was upgraded and installed in 2021.

System Specifications (2021-present)

FACP

The building is protected by a Notifier NFS2-640C hybrid-addressable fire alarm system. The panel is located in the main lobby of Arena 2. The system runs Notifier's FlashScan addressable protocol, and utilizes several Notifier XP6-MAA zone cards to accommodate conventional devices. The system coding is temporal.

Notification Appliances

Most notification appliances are System Sensor "L-Series" P2RLA-E horn/strobes (red, wall-mount, English lettering, set to 15cd).
Arena 1 has System Sensor PC2RLA-E horn/strobes (red, ceiling-mount, English lettering, set to 15cd) for additional coverage.
Some areas have System Sensor SRLA-E remote strobes (red, wall-mount, English lettering, set to 15cd).

Initiating Devices

Pull Stations

All pull stations in Arena 1 are Notifier NBG-12LX addressable dual-action pull stations.
All pull stations in Arena 2 are Notifier MPS-950B conventional single-action pull stations.

Automatic Detection Devices

There are Notifier FSP-951A addressable photoelectric smoke detectors at the top of each stairwell and at each end of the club level in Arena 1, mounted on System Sensor B300A-6 bases.
There are Chemtronics 601 conventional 135°F fixed-temperature/rate-of-rise heat detectors in each washroom in Arena 2.
There are heat detectors in each change room in Arena 2, likely FDD CR-135.

Modules

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches in Arena 1, as well as the kitchen suppression system.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on all SLCs.

EOLs

There are Notifier EOL-CR end of line resistor plates on all conventional, sprinkler and signal circuits.