The Arch Apartments

From FireAlarmPedia
Revision as of 15:33, 6 March 2026 by TwentyThree33 (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Mircom FX-2000<br />FACP Location: Fire Control Room<br />System Type: Single-Stage Addressable<br />System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (Audible)<br>24VFWR (Visual)<br />System Coding: Temporal Tone<br>Strobes Synchronized: No<br />Date of last known Upgrade: N/A<br />Most Recent Known Modification: 2026, Speaker<br />Year Opened: 2015 |} '''The Arch''' is a hig...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Mircom FX-2000
FACP Location: Fire Control Room
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 70.7VRMS (Audible)
24VFWR (Visual)
System Coding: Temporal Tone
Strobes Synchronized: No
Date of last known Upgrade: N/A
Most Recent Known Modification: 2026, Speaker
Year Opened: 2015

The Arch is a high-rise apartment building located at 1115 9 St SW, in Calgary, Alberta, Canada. The building is owned and operated by Boardwalk. The building was built in 2015, and the fire alarm system is original.

System Specifications

FACP

The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located in the fire control room, behind the mail room on the main floor. The system runs Mircom's CLIP addressable protocol, and is equipped with Mircom's QX-5000 voice evacuation system. The evacuation signal is a temporal tone.

Booster Panels

There are Mircom BPS-1100 11-amp booster power supplies in the electrical rooms on the 4th, 8th, 12th, 16th, 20th and 23rd floors.

Notification Appliances

All common areas have System Sensor "SpectrAlert Advance" SPSCWA speaker/strobes (white, ceiling-mount, set to 70V/15cd).
All suite bedrooms have Mircom SP-404-70A remote speakers (white, 4" square) equipped with Mircom SSW-100 silence switches.
All stairwells have Mircom SP-204A-70W remote speakers (white, 4" square).

Initiating Devices

Pull Stations

All pull stations are Mircom MS-401AD addressable single-action pull stations.

Automatic Detection Devices

There are Mircom MIX-2251APA addressable photoelectric smoke detectors in all corridors, at the top and on every third floor of each stairwell, and in all elevator lobbies.
There are Mircom MIX-5251RAPA addressable 135°F fixed-temperature/rate-of-rise heat detectors at the top of each elevator shaft.
All detectors are mounted on System Sensor B210LPA bases.
There are System Sensor "InnovAir Flex" DNRA duct smoke detector housings equipped with Mircom MIX-2251APA addressable photoelectric heads on all makeup air units.

Firefighter's Telephones

There are Mircom FT-300A fire phones at each stairwell on each floor.

Modules

There are Mircom MIX-M500MAPA addressable monitor modules supervising the fire pump's run/trouble contacts, the generator's run/trouble contacts, all boosters, and the sprinkler system's tamper and flow switches.
There are Mircom MIX-M500RAPA addressable relay modules serving various purposes.
There are Mircom MIX-M500FPA fire phone modules controlling all fire phones.
There are System Sensor M500XA isolator modules on all 4 SLCs.

EOLs

There are Mircom MP-300 end of line resistor plates on all circuits supervised by monitor modules, and on all signal circuits.