System Specifications |
---|
FACP: Notifier NFS-320 FACP Location: Lobby, Left of Entrance System Type: Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, SS Date of last known Upgrade: N/A Year Opened: 2009 |
Sleep Inn & Suites is an American chain of hotels. This particular hotel is located at 3200 Outlet Blvd, Idaho Falls, ID. It was built in 2009, and the fire alarm system is original.
System Specifications (2009-present)
FACP
The building is protected by a Notifier NFS-320 addressable fire alarm system. The panel is located in the lobby, on the left side of the entrance. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.
Notification Appliances
All notification appliances are from System Sensor’s “SpectrAlert Advance” line of products.
All common area notification appliances are System Sensor P2W horn/strobes (white, wall-mount, set to 15cd).
The pool area has System Sensor P2RK weatherproof horn/strobes (red, wall-mount, set to 75cd).
There are System Sensor SW remote strobes (white, wall-mount, set to 15cd) in areas requiring more visual coverage.
Each guest room and the weight room have System Sensor HW horns (white, wall-mount).
Initiating Devices
Pull Stations
Most pull stations are Notifier NBG-12LX addressable dual-action pull stations.
The pool area has Notifier NBG-12LXO weatherproof addressable dual-action pull stations.
Automatic Detection Devices
There are Notifier FSP-851 addressable photoelectric smoke detectors throughout the hotel, mounted on System Sensor B501 bases. There is also a sprinkler system.
Modules
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.