Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

Paradise Chalet (Marmot Basin)

From FireAlarmPedia
System Specifications
FACP: Notifier System 5000
FACP Location: Main Entrance
System Type: Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Continuous
Date of last known Upgrade: N/A
Year Opened: 1991

Marmot Basin is an alpine ski resort located in Jasper National Park, AB. It is located 20 minutes away from Jasper. The resort has 91 ski runs, 6 chairlifts, and three daylodges. This page will cover the Paradise Chalet, which is located mid-mountain in the same building with Eagle Chalet. This daylodge was built in 1991, and still retains its original fire alarm system. The two lodge's fire alarm systems are NOT connected.

System Specifications (1991-present)

FACP

The building is protected by a Notifier System 5000 conventional fire alarm system. The panel is located in the main entrance, and has a capacity for 24 zones, 12 zones are in use. The lock on the cabinet has been busted, and is held shut with copper wire. The system coding is continuous.

The System 5000 may be too big, but was installed likely due to supply issues.

Notification Appliances

Most notification appliances except one are Notifier KMS-10-24VDC/P motor bells (10” gong).

In the basement, there is a Notifier KMS-6-24VDC/P motor bell (6" gong).

Initiating Devices

Pull Stations

All pull stations are Notifier FM-950B conventional pull stations (black label).

Automatic Detection Devices

The lodge is protected by a sprinkler system with waterflow, therefore there are no detectors present.