FACP: Notifier NFS-320C FACP Location: Main Entrance Vestibule System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: 2023 Year Opened: 2008 |
Lincoln Park Centre is a medical and professional office building located at 5 Richard Way SW, Calgary, AB. The building was completed in 2008 and the fire alarm system is mostly original, with a third floor upgrade taking place in 2023.
System Specifications (2008-present)[edit | edit source]
FACP[edit | edit source]
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.
Booster Panels[edit | edit source]
There are two Notifier FCPS-24S8C 8-amp booster power supplies on the system. One is located above the ceiling in the north hallway, and the other is in the third floor tenant electrical room.
Notification Appliances[edit | edit source]
Most notification appliances on the first two floors are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd).
The third floor has System Sensor “L-Series” P2RLA horn/strobes (red, wall-mount, set to 15cd/electromechanical), as well as System Sensor PC2RLA horn/strobes (red, wall-mount, set to 15cd/electromechanical); the former can also be found as deficiency replacements.
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules.
Automatic Detection Devices[edit | edit source]
There are Notifier FSP-851A addressable photoelectric smoke detectors in the stairwells and elevator lobbies.
The electrical closets have Notifier FST-851A addressable 135°F fixed-temperature heat detectors.
There are Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detectors in the elevator shafts.
The main electrical room has a Notifier FST-851HA addressable 190°F fixed-temperature heat detector.
All above detectors are mounted on Notifier B710LPA bases.
The air handling units have Notifier FSD-751PLA addressable photoelectric duct smoke detectors.
Modules[edit | edit source]
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on the SLC.
EOLs[edit | edit source]
There are Notifier EOL-CR end-of-line resistor plates on all sprinkler and signal circuits.