Maxwell Bates Block

From FireAlarmPedia
System Specifications
FACP: Notifier NFS-320C
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: 2023
Year Opened: 2013

Maxwell Bates Block is a mixed-use commercial building located at 2207 4 Street SW, Calgary, Alberta. The complex was built in 2013, and the top floor was renovated in 2023. The fire alarm system is original, with new devices in the renovated area.

System Specifications (2013-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.

Notification Appliances[edit | edit source]

Most notification appliances are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd).
The third floor has System Sensor “L-Series” SRLA remote strobes (red, wall-mount, bilingual lettering, set to 15cd).
For exterior notification, there is a System Sensor SRKA weatherproof remote strobe (red, wall-mount, set to 75cd).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

Most pull stations are Notifier N-MPS-SC conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules.
There are some Notifier N-MPS-SA addressable single-action pull stations as deficiency replacements.

Automatic Detection Devices[edit | edit source]

Most smoke detectors are Notifier FSP-851A addressable photoelectric smoke detectors, found in the elevator lobbies, stairwells, closets, third floor, and server rooms.
The electrical rooms, bathroom area of Phil + Sebastian, and parkade storage room have Notifier FST-851RA addressable 135°F fixed/rate-of-rise heat detectors.
All above detectors are mounted on System Sensor B210LPA bases.
The third floor has Notifier FSP-951A addressable photoelectric smoke detectors, mounted on System Sensor B300A-6 bases.
There are two System Sensor DNRA duct smoke detector housings on the rooftop unit for supply and return. The supply has a Notifier FSP-851A addressable photoelectric head, and the return has a Notifier FSP-951A addressable photoelectric head as a deficiency replacement.

Modules[edit | edit source]

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on the SLC.

EOLs[edit | edit source]

There are Notifier EOL-CR end-of-line resistors on all sprinkler and signal circuits.