| System Specifications |
|---|
| FACP: Mircom FX-2000 FACP Location: Unknown System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Temporal Strobes Synchronized: Unknown Date of last known Upgrade: 2023 Year Opened: 1976, 2023 |
Canada Diagnostic Centres is a Canadian chain of radiology clinics. This particular clinic is located inside the City Centre Mall (Leduc) at #1 5201 50 Street, in Leduc, Alberta, Canada. The building was built in 1976, and the clinic opened in 2023. The fire alarm system was installed in 2023.
System Specifications (2023-present)
FACP
The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel location is unknown. The system runs Mircom’s Advanced addressable protocol, and the system coding is temporal.
This system is tied to the main mall system, and will initiate an alarm on that system when activated.
Notification Appliances
All notification appliances are Mircom FHS-400C-RR horn/strobes (red, ceiling-mount, set to 15cd).
Initiating Devices
Pull Stations
All pull stations are Mircom MS-401AP addressable single-action pull stations.
Automatic Detection Devices
None noticed.
Modules
There are Mircom MIX-M500MAPA addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are System Sensor M500XA isolator modules on the SLC.
EOLs
There are Mircom MP-300 end of line resistor plates on all sprinkler and signal circuits.